Siemens SITRANS P Series Supplement To Operating Instructions page 14

Pressure transmitter
Hide thumbs Also See for SITRANS P Series:
Table of Contents

Advertisement

2. Press the "Start PROFIsafe Commissioning" button.
3. Press the "Close" button.
Result
The "Start PROFIsafe Commissioning" dialog box is closed.
The PROFIsafe device is in "S2" and is write protected accordingly.
Checksum PROFIsafe Commissioning
1. Press the "Upload to PG/PC" button.
2. Click on "Device > PROFIsafe Commissioning > Checksum for PROFIsafe
3. Press the "Start generation of checksum" button.
4. If the checksums are equal, press the button "The checksums are equal!".
5. Press the "OK" button.
Result
The "Checksum PROFIsafe Commissioning" dialog box is closed.
Note
Before you continue the PROFIsafe commissioning, carry out all necessary function checks,
which ensure the correct functioning of the device in its application.
Continue after function check
1. Click on "Device > PROFIsafe Commissioning > Continue PROFIsafe Commissioning" in
2. Press the "Inspection completed" button.
SITRANS P, DS III PROFIsafe series
Supplement to Operating Instructions, 03/2006, A5E00732533-01
The PROFIsafe Commissioning State shows: "S2 = intended for safe operation, not
inspected"
Commissioning" in the menu bar.
The "Checksum PROFIsafe Commissioning" dialog box is opened.
Additional information is then displayed.
If the checksums are not equal, press the button "The checksums are different!".
Additional information is then displayed.
the menu bar.
The "Continue PROFIsafe Commissioning" dialog box is opened.
The PROFIsafe Commissioning State shows: "S2 = intended for safe operation, not
inspected"
The PROFIsafe Commissioning State shows: "S3 = intended for safe operation,
inspection completed"
PROFIsafe
1.7 PROFIsafe Commissioning