5.10. FV-200PS-AS DC Power Supply Panel

The FV-200PS-AS supplies 24 V DC power to each unit used in FV-200 series Emergency Public Address
System. In additional, the FV-200PS-AS shall connect to an emergency power supply for uninterrupted DC
power during AC power failure.
1. AC Power Indicator
Lights green when AC power is supplied and the
FV-200PS-AS is ready for operation on AC power.
[Rear]
220-230V~ 50/60Hz 160W
3
3. AC Power Inlet
Connect the supplied power cord to this inlet.
4. 24V DC Output Terminal
Connect this terminal to the 24 V DC input of each
system unit. Current capacity: 5 A (total).
(M4 screw terminal; barrier distance: 12 mm)
DC POWER OUTPUT
24V
(TOTAL MAX.5A)
NC
4
2. DC Power Indicator
Lights orange when DC power is supplied and the
FV-200PS-AS is ready for operation on DC power.
BATTERY POWER IN
24V MAX. 5A
5
5. Battery Power In Terminal
Connect to battery or Emergency Power Supply
panel.
(M3 screw terminal; barrier distance: 6.4 mm)
6. Function Earth Terminal
Connect this terminal to the functional earth termi-
nal of external equipment if excessive noise is
generated when the external equipment is
connected to the FV-200PS-AS. This could reduce
noise.
Note: This terminal is not for protective earth.
1
2
DC
AC
POWER SUPPLY PANEL FV-200PS-AS
GROUND
6
19