Emerson Rosemount 975MR Reference Manual page 64

Multi-spectrum infrared flame detector
Hide thumbs Also See for Rosemount 975MR:
Table of Contents

Advertisement

Accessories
August 2019
NOTICE
The item letters in this procedure can be found in
Procedure
1. Place the flame simulator in a safe area, not exceeding 104 °F (40 °C).
2. Release the locking screw.
3. Unscrew the battery back cover (D) counter-clockwise.
4. Unscrew the locking disc (C) clockwise.
5. Pull out the battery from the flame simulator.
6. Connect the battery to the charger.
7. Charge for a maximum of two to three hours.
8. Disconnect the charger.
9. Insert the battery in the flame simulator.
10. Screw on the locking disc (C).
11. Screw on the back cover (D).
12. Lock the back cover with the locking screw.
D.1.6
Replace the battery
NOTICE
The item letters shown in this procedure can be found in
Procedure
1. Place the flame simulator on a table in a safe area, not exceeding 104 °F (40 °C).
2. Release the locking screw.
3. Unscrew the battery back cover (D) counter-clockwise.
4. Unscrew the locking disk (C) clockwise.
5. Pull out the battery from the flame simulator.
6. Insert the new battery pack in the simulator housing.
7. Screw on the locking disc (C).
8. Screw on the back cover (D).
9. Lock the back cover with the locking screw.
64
Use only Rosemount battery pack, PN 00975-9000-0012.
NOTICE
For more information, refer to 00809-0500-4975.
Reference Manual
Figure
D-2.
Figure
D-2.
Emerson.com/Rosemount
00809-0100-4975