1 0 | Bosch IDS BOVA
6
Refrigerant line routing
6.1
Precautions
Take precautions to prevent noise within the building structure due to
vibration transmission from the refrigerant lines. For Example:
When the refrigerant lines have to be fastened to floor joists or
other framing in a structure, use isolation type hangers.
Isolation hangers should also be used when refrigerant lines are
run in stud spaces or enclosed ceilings.
Where the refrigerant lines run through a wall or sill, they should
be insulated and isolated.
Isolate the lines from all ductwork.
Minimize the number of 90º turns.
Side View
Secure Suc tion li ne from joists us ing isolators every 8 ft . Secure
Liquid Line directly to Suc tion li ne using tape, wire, or other
approp riate method every 8 ft.
Figure 12
Side View
Secure Suc tion Line using isolators every 8 ft . Secure Liqu id Line
directly to Suc tion Line using tape, wire, or other approp riate
method every 8 ft.
Figure 13
Data subject to change
8 Feet Maximum
8 Feet Maximum
Isolation From Joist/Rafter
8 Feet Maximum
8 Feet Maximum
Isolation In Wall Spaces
Comply with National, State, and Local Codes when isolating line sets from
joists, rafters, walls, or other structural elements.
12.2016 | Bosch Thermotechnology Corp.
Installation Instructions
Jo ist/Raft er
Isolator
Line Set
Wall
Isolator
Line Set