System Charge Adjustment; Charging: Weigh-In Method; Subcooling Charging And Refrigerant Adjustment In Cooling (Above 55°F Outdoor Temp.) - Bosch IDP Premium 18 SEER2 Series Installation Instructions Manual

Inverter ducted packaged heat pump
Table of Contents

Advertisement

Installation Instructions

12 System Charge Adjustment

The unit comes precharged from the factory with 7-8 lb-oz of
refrigerant. Follow Section 12 for charge adjustments i.e if components
have been replaced, or if there is a suspected leak.

12.1 Charging: Weigh-In Method

Weigh-in method is recommended anytime a system charge is being replaced.
Weigh-in method can also be used when power is not available to the equipment site
or operating conditions (indoor/outdoor temperatures) are not in range to verify
with the subcooling charging method.
Heat Pump Model
BRBA-36HWD1N1-M18
Table 13
12.2 Subcooling Charging and Refrigerant Adjustment In Cooling
(Above 55°F Outdoor Temp.)
1.
Check the outdoor ambient temperatures.
Subcooling (in cooling mode) is the only recommended method of
charging above 55°F outdoor ambient temperatures. For outdoor ambient
temperatures below 55°F, use weigh-in charge method.
It is important to return in the spring or summer to accurately charge
the system in the cooling mode when outdoor ambient temperature is
above 55°F.
Outdoor
Temperature
Above 55ºF
120ºF
55ºF
Outdoor Temp1
Figure 23
For best results the indoor temperature should be kept between 70°F to 80°F.
2 0 |
Refrigerant Charge (lb-oz)
8-6
Outdoor
Temperature
Below 55ºF
55ºF
Outdoor Temp2
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump - BTC 761703103 A (11.2022)
80 ºF
70ºF
Indoor Temp
Figure 24
2.
Stabilize the system.
After starting the system in cooling mode, short press "FORCE" button,
3.
and a "    | — " symbol should appear. System may take 10 minutes to ramp up.
Operate the system for a minimum of twenty (20) minutes.
Figure 25
SW1 is not used.
After a twenty (20) minute stabilization period operating at 100%
capacity (72 Hertz ), maintain continuous operation while adjusting
refrigerant charge. After adjusting, operate system for a minimum of
fi ve (5) minutes for system to stabilize, otherwise repeat step 3.
20 MIN.
Figure 26
4.
Calculate subcooling value on liquid line (According to Table 14)
Measured Liquid Line Temp. = ________ºF
Measured Liquid Line Pressure = _______ PSIG
Calculate subcooling value = ________ºF