6 | Bosch IDS BOVA
2

Unit location considerations

2.1
Unit dimensions
Unit Dimensions
Models
BOVA-36
BOVA-60
Table 1
The unit's weight values is on the carton box.
When mounting the outdoor unit on a roof, be sure the roof will support the unit's
weight. Properly selected isolation is recommended to prevent sound or vibration
transmission to the building structure.
Figure 1
Data subject to change
H x W x L (Inches)
24-15/16 x 29-1/8 x 29-1/8
33-3/16 x 29-1/8 x 29-1/8
W
H
L
2.2
Refrigerant piping limits
Maximum line equivalent length = 100 feet.
Maximum vertical equivalent length = 50 feet.
Use only the line diameters indicated in Table 5.1.
If the suction line sets are greater than 60 feet do not use a larger suction
line than recommended.
Figure 2
Installation Instructions
Standard Line
Set 100' Max
Line Length
50' Max
Line Lift
12.2016 | Bosch Thermotechnology Corp.