Refrigerant Line Routing; Precautions - Bosch IDS BOVB20 Installation Instructions Manual

Split system heat pump
Table of Contents

Advertisement

7 Refrigerant Line Routing

7.1 Precautions

Take precautions to prevent noise within the building structure due to
vibration transmission from the refrigerant lines. For example:
When the refrigerant lines have to be fastened to floor joists or
other framing in a structure, use isolation type hangers.
Isolation hangers should also be used when refrigerant lines are
run in stud spaces or enclosed ceilings.
Where the refrigerant lines run through a wall or sill, they should
be insulated and isolated.
Isolate the lines from all ductwork.
Minimize the number of 90º turns.
Side View
Figure 14
Side View
Figure 15
Bosch IDS BOVB20 Split System Heat Pump - BTC 761701316 C (02.2022)
8 Feet Maximum
8 Feet Maximum
Secure Suction Line from joists using isolators every 8 ft. Secure Liquid Line
directly to Suction Line using tape, wire, or other appropriate method every 8 ft.
Isolation From Joist/Rafter
8 Feet Maximum
Secure Suction Line using isolators every 8 ft. Secure Liquid Line directly to
Suction Line using tape, wire, or other appropriate method every 8 ft.
Isolation On Walls
  Comply with National, State, and local codes when isolating linesets
from joists, rafters, walls, or other structural elements.
8 Feet Maximum
Installation Instructions
Joist/Rafter
Isolator
Lineset
Wall
Isolator
Linesets
| 13

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ids bovb36-20Ids bovb60-20

Table of Contents