In addition, you may configure any relay independently and program it to
activate pumps or control valves.
As process alarms, alarm logic (high or low activation or USP*) and
deadband are user-programmable. Customer-defined failsafe operation is
supported as a programmable menu function to allow all relays to be
energized or not energized as a default condition upon powering the
transmitter. You may program the USP* alarm to activate when the
conductivity is within a user-selectable percentage of the limit. USP*
alarming is available only when a contacting conductivity measurement
board is installed.
3.2
Prepare conduit openings
There are six conduit openings in all configurations of the transmitter.
Note
Emerson fits four of openings with plugs upon shipment.
Figure 3-1: Conduit openings
A. Front panel/keypad
B. Power leads
C. Alarm relay leads
D. Sensor 1 cable
E. 4-20 mA/HART
F. Sensor 2 cable
G. Spare opening
Note
Always use proper cable gland fittings and plugs for wire and cable
installations.
Conduit openings accept ½-in. conduit fittings or PG13.5 cable glands. To
keep the case watertight, block unused openings with Type 4X or IP66
conduit plugs.
Quick Start Guide
®
®