DTC 200/2G
Trouble shooting guide
TROUBLE
The pump is not operating irrespective
of temperature
The pump operating permanently
irrespective of temperature
The pump and burner operating
p e r m a n e n t l y i r r e s p e c t i v e o f
temperature
Temperature regulation of DHW tank
is not working
In spite of enough collector's energy
the water temperature in DHWT is not
high enough – water is too cold
The temperature is reached, but the
heating/cooling is still running
In AUTO position nothing happens
Advantages of motor actuated ball valves of EMV110..series with incorporated relay
module for solar heating systems
In solar heating systems motor actuated ball valves can prevent
various inconveniences.
o Effectively prevent hydraulic shocks in systems as they require
30 seconds for complete opening.
o Due to their shape they do not impede the flow.
o Springs are not included, therefore noise does not appear.
o When closed, 100% sealing is guaranteed.
o They have an output for pump up to 100 W in open position,
therefore they do not present a hydraulic load for pump in
closed position. They enable pump switching on only in
completely open position.
o Due to installed RELAY module they enable control with make
contact only.
o If during closing or opening process impurities enter in valve,
which could block it, the valve stops and immediately afterwards
continues with opening or closing process in opposite direction,
so that water flow can rinse the impurities up to cleaning net
(anti-blocking system).
o Possibility of manual control. This function relieves airing the
system or filling the system with water.
o It prevents coaxial cooling of DHWT by one pipe in night-time.
For preventing coaxial
cooling in night-time it
is necessary to build in
motorised ball valve EMV
110... in heating pipe of
DHW tank exchanger.
80
page
POSSIBLE FAILURE
- Power supply is not connected
- Selector switch is in position OFF
- DHWT sensor T2 is disconnected
- Collector sensor T1 is short circuited
- Selector switch is in position ON1
- Collector sensor T1 is disconnected
- DHWT sensor T2 is short circuited
- Selector switch is in position ON1+2
- Collector sensor T1 is disconnected
- DHWT sensor T2 is short circuited
- Motorised ball valve is permanently open
or nonreturn valve is open (thermosiohon
water circulation is enabled)
-Setting of DHWT temperature is too low
-The difference setting is set to high
- Jumpers are not set correctly
- Jumpers are pulled out
HOT WATER
COLD WATER
REMEDY
- Check power supply
- Set the selector switch in position AUTO
- Check sensor
- Check sensor
- Set the selector switch in position AUTO
- Check sensor
-Check sensor
- Set the selector switch in position AUTO
- Check sensor
- Check sensor
Check the installation
-Check settings
- Check jumper's settings
- Set jumpers in suitable position
EMV 110 602/4230
EMV 110 316/89I0
In night-time the temperature of water in DHWT
is usually higher than in collector. In this case it is
possible coaxial cooling of the DHWT through one
pipe. If the pipe has enough diameters and it is
straight and vertical, then water circulation begins
in just one pipe. In the middle, water goes upwards,
and at the edges downwards.
One solution for this is to build in nonreturn valve.
But with its use is increased the load of pump, the
flow reduced, and the ventilation of the system
hindered.
All these problems are solved by the motorised ball
valve series EMV 110 ...