Watchdog Functionality - ABB SAM600 Operation Manual

Process bus i/o system
Hide thumbs Also See for SAM600:
Table of Contents

Advertisement

1MRK 511 434-UEN B
System topology error
Loss of synchronization to an external clock
Time synchronization state not as configured
Digital input voltage error (SAM600-CT and SAM600-VT only)
SAM600 system bus link error
Fatal module failure
All modules in the SAM600 system will react to an error condition (locally detected or
announced by another module):
If a topology error is announced, the SAM600 module will set the red LED to steady ON.
If a topology error is announced and the SAM600 module's time synchronization mode is
Free-running , the SmpSync field value of all sampled value streams (except bridged
streams) on all uplink ports of the SAM600 module is set to (0).
If a topology error or peer delay error is reported and the SAM600 module's time
synchronization mode is
synchronized to an absolute time source, then the SmpSync field value of all sampled
value streams (except bridged streams) on all uplink ports of the SAM600 module is set to
(0).
All SAM600 modules in the SAM600 system return to their normal behavior when the error
condition is cleared on the announcing SAM600 module.
2.3.11

Watchdog functionality

A watchdog functionality is available on SAM600-TS. The watchdog is activated in case of a
device error on SAM600-TS or a severe error condition announced by any module in the
SAM600 system. Error conditions announced in the SAM600 system are listed in
The SAM600-TS module will operate the watchdog if any one of these conditions is announced
in the system or detected locally. Once the error condition is cleared, the SAM600-TS module
will automatically reset the watchdog.
In case the SAM600 system bus is configured as HSR ring the behaviour of the watchdog
regarding SAM600 system bus link errors is configurable. The parameter "
system bus single redundancy error " controls whether the watchdog is operated on a single
link error or double link error. Default value of the parameter is FALSE, which means the
watchdog is not operated in case of a single link failure in the SAM600 system bus. Due to the
communication redundancy of the HSR ring such a single link error has no impact on the
system functionality.
Nevertheless, the user can set the parameter value to TRUE, in which case a single link failure in
the SAM600 system bus will trigger the watchdog. Double link failures, i.e. a module has no
connection to the SAM600 system bus on either of its two ports, will always trigger the
watchdog.
The parameter "
the Parameter Setting Tool of PCM600. The parameter is system-wide, i.e. all SAM600-TS
modules will operate their watchdog in the same way.
SAM600 Process Bus I/O System
Operation Manual
Master Clock and the SAM600 module is currently not
The watchdog error indication is not sticky. Once the error condition is cleared
the SAM600-TS module will reset the watchdog automatically after ca. 20
seconds.
Open IRF contact on system bus single redundancy error " can be configured in
© Copyright 2017 ABB. All rights reserved
Section 2
SAM600 Process Bus I/O System
GUID-C8F7FD39-637B-4D15-9F48-48A8C57D25DE v1
Section
2.3.10.
Open IRF contact on
25