Functional Description; Distributed Analog Sampling - ABB SAM600 Operation Manual

Process bus i/o system
Hide thumbs Also See for SAM600:
Table of Contents

Advertisement

1MRK 511 434-UEN B
(a)
Grandmaster
(c)
SAM600
IEC18000517 V2 EN-US
Figure 6:
2.3

Functional description

2.3.1

Distributed analog sampling

SAM600-CT and SAM600-VT modules convert analog input values from secondary protection
or measurement cores (1A/5A – order variant, or 100V-125V AC, settable, respectively) to a
digital format transmitted over Ethernet according to IEC 61850-9-2, following the UCA
implementation guideline 2004. Inputs are converted following the IEC 61869-9 standard for
protection and operational metering applications. The amplitude accuracy and phase
displacements for the analog input channels for both SAM600-CT and SAM600-VT are
specified in the SAM600 product guide (1MRK 511 437-BEN).
SAM600 Process Bus I/O System
Operation Manual
IED Ctrl
Clock
9-2LE
1PPS
IED Prot
9-2LE
IED
Busbar
IEEE 1588
9-2LE
SAM600
SAM600
CT
VT
9-2LE (HSR)
1PPS
SAM600
SAM600
TS
TS
CT
Communication architectures for SAM600 process bus I/O system
© Copyright 2017 ABB. All rights reserved
(b)
Grandmaster
Clock
IEEE 1588
SAM600
TS
IED Ctrl
IED Prot
9-2LE
IED
Busbar
SAM600
VT
SAM600 Process Bus I/O System
IED Ctrl
IED Prot
9-2LE (HSR)
9-2LE
IED
Busbar
1PPS
SAM600
SAM600
CT
VT
GUID-483BD0F3-9125-4A66-B64A-94EF58482A8E v1