Electrical connection
6.3 Connecting the grounding conductor
6.3.1
Grounding connection type
Enclosure grounding method
Connection of an individual conductor under the ex‐
ternal grounding bracket.
Connection is made using a DIN cable lug under the
external grounding bracket. DIN 46 234
6.3.2
Minimum surface area of grounding conductor
Table 6-3
Minimum cross-section of the phase conductor for
Internal ground terminal
When making connections, ensure the following:
● Ensure that the connecting surface is bare and is protected against corrosion using a
suitable substance, e.g. acid-free Vaseline.
● Arrange the flat washer and spring washer under the bolt head.
● Locate the cable lug under the clamping bracket.
● Use the terminals designated for the grounding conductor in the terminal box.
● Observe the tightening torque for the locking screw.
56
Minimum cross-sectional area of grounding conductor
installation
S
[mm²]
S ≤ 25
25 < S ≤ 50
S > 50
Minimum cross-section of the associated ground‐
ing connection
[mm²]
S
25
0.5 S
1PC134, 1PC136 crane motors SH 132 ... 315
Operating Instructions, 02/2019, A5E43212221A
Conductor cross-
section
mm²
... 10
... 25