Grounding Connection Type; Minimum Surface Area Of Grounding Conductor; Ground Connection Inside And Outside - Siemens SIMOTICS A 1FU8 Operating Instructions Manual

Synchronous motors
Table of Contents

Advertisement

Available languages

Available languages

6.4.2

Grounding connection type

Enclosure grounding method
Connection of an individual
conductor under the external
grounding bracket.
Connection is made using a
DIN cable lug under the
external grounding bracket.
DIN 46 234
6.4.3

Minimum surface area of grounding conductor

Table 6- 5
Minimum cross-sectional area of phase conduc-
6.4.4

Ground connection inside and outside

Internal ground connection
When making connections, ensure the following:
● Ensure that the connecting surface is bare and is protected against corrosion using a
suitable substance, e.g. acid-free Vaseline.
● Arrange the flat washer and spring washer under the bolt head.
● Locate the cable lug under the clamping bracket.
● Use the terminals designated for the grounding conductor in the terminal box.
● Comply with the tightening torque for the terminal screw.
1FU8
Operating Instructions, 02/2016, 5 610 70000 02 000
Minimum cross-sectional area of grounding conductor
tor for installation
S
[mm²]
S ≤ 16
16 < S ≤ 35
S > 35
6.4 Connecting the grounding conductor
Minimum surface area of associated grounding
connection
[mm²]
S
16
0.5 S
Electrical connection
Conductor
cross-
section
[mm²]
... 10
... 25
61