LG RCWW-1 Operation & Maintenance Manual page 38

Water-cooled screw r134a
Table of Contents

Advertisement

Flow Rate
Basic flow rate of the chiller follows the value indicated on the table showing the maximum, minimum and
design flow rate. Higher or lower flow rate is permitted to achieve lower or high rise in temperature. To ensure
appropriate heat exchange and turbulence Within the evaporator and condenser, the flow rate must exceed the
minimum flow rate.
◆ Evaporator
MODEL
RCWW200RAAA
◆ Condenser
MODEL
RCWW200RAAA
Chiller Water-cooled Screw
Min
gpm
l/s
411.17
25.94
Table 9
Min
gpm
l/s
363.68
22.95
Table 10
- 38 -
Norminal
gpm
l/s
519.54
32.78
Norminal
gpm
l/s
587.39
37.06
Max
gpm
l/s
763.60
48.18
Max
gpm
l/s
675.40
42.61