Model
SL 26-260 G3
SL 40-399 G3
If the value is less than anticipated, verify combustion.
If low fire CO
Note: This can be done only after high fire calibration has been set and verified.
Adjust the low fire using the zero-offset adjustment screw (Low Fire adjustment). Note:
This adjustment is sensitive and should only be attempted after consulting with IBC
technical support.
To access the adjustment screw, remove the #15 Torx Cap.
Adjust the nylon screw as specified below:
d. Once complete, use the Back button to navigate to the Main Menu.
5. Set the Load type back to your desired load type.
a. Do the following:
6
|
Flame Minimum Signal
Minimum Raw
Value
498
871
is out of calibration, contact IBC technical support: 1-844-432-8422.
2
Only adjust the zero-offset adjustment in 1/8
analyzer to stabilize.
Never adjust the zero-offset adjustment greater than 1/2 of a revolution in either
direction unless directed by the IBC technical support.
Anticipated Raw
µA
Value
Min.
871
2.0
1, 195
3.5
th
turns or less and wait for your
Anticipated
Value µA
>3.5
>4.8