IBC SL G3 Series Commissioning Supplement page 5

Boilers with side piping

Advertisement

a. Change the heat output in the Installer Settings.
Go to the
load type > In the
select Save > Create a demand for heat > Select the Back button to return to the Main Menu.
b. Check the low fire (Flame Current) µA.
To check the flame current, go to the Main Menu >
Status >
Flame Current.
c. Identify the μA.__________
Low Fire μA should be greater than the minimum values prescribed in the table below.
Model
SL 10-85 G3
SL 14-115 G3
SL 20-160 G3
SL 30-199 G3
www.ibcboiler.com
Main Menu > Installer Settings > Select the
Heat Output box, change the value to the minimum firing rate, and
Flame Minimum Signal
Minimum Raw
Value
400
498
600
498
Edit button next to the Manual
Diagnostics >
Anticipated Raw
µA
Value
Min.
548
1.6
871
2.0
946
2.4
871
2.0
SIM Menu >
Anticipated
Value µA
>2.2
>3.5
>3.8
>3.5
5