Cleaning procedures

Avoid risk for cutting injury by wearing the proper protective equipment !
WATER DISTRIBUTION PIPE AND STRAINERS
The water distribution piping of the adiabatic pre-cooling section is supplied with in line water filters, filtering water
particles from the incoming water.
Some solids in the water may accumulate in the water distribution header and need to be rinsed out at least twice a
year. Also the city water filters or strainers need to be cleaned out at least once per month as follows: remove
water filter access cap, remove strainer mesh and rinse mesh with clean water.
The recommended procedure for cleaning of the water distribution header is:
1. Remove all the pre-cooling media from the pre-cooler section to give access to the water distribution header
ends. Refer to "Cleaning procedures", section "Adiabatic pre-cooling media", subsection "Removal and
replacement".
2. Unscrew the flexible sleeve connection by loosening the sleeve clamps. Use a 7 mm spanner or other
appropriate tool.
22
W W W . B A L T I M O R E A I R C O I L . E U
CAUTION
Stainless steel parts can be sharp.
Water filter