Water quality guidelines for adiabatic
pre-cooler frame
Temperature
PH
Hardness as (CaCO
)
3
Alkaline as (CaCO
)
3
Total dissolved solids
Chlorides
Sulfates
Conductivity
Bacteria Rate (CFU/ml, KBE/ml)
For Ozone water treatment application, stainless steel 316L execution is required.
Model
DFCV-EC9122-*
DFCV-EC9123-*
DFCV-EC9124-*
DFCV-EC9125-*
DFCV-EC9126-*
DFCV-EC9127-*
If any of the following happens:
•
at ambient conditions exceeding the given maximum ambient conditions,
•
with supply water quality data exceeding one or more of the concentration limits of above table "Minimum
supply water quality",
•
if the supply water has a Practical Scaling Index below 5.5,
Then:
•
the water flow needs to be increased to higher levels to avoid rapid fouling and scaling of the pre-cooler
medium. Contact your local BAC-Balticare representative for support.
3 Water care
3 Water care
Minimum supply water quality
Number of fans
4 fans
6 fans
8 fans
10 fans
12 fans
14 fans
Recommended adiabatic pre-cooler water flow rates
Baltiplus 800™ coating
< 20 ºC
6.5 – 9
50 – 500 mg/l
< 500 mg/l
< 1500 mg/l
< 200 mg/l
< 250 mg/l
1800 µS/cm
< 1000
Minimum pre-cooler water flow
per unit
14 l/min
22 l/min
28 l/min
36 l/min
44 l/min
50 l/min
W W W . B A L T I M O R E A I R C O I L . E U
9