Water quality guidelines for adiabatic
pre-cooler frame
Temperature
PH
Hardness as (CaCO
)
3
Alkaline as (CaCO
)
3
Total dissolved solids
Chlorides
Sulfates
Conductivity
Bacteria Rate (CFU/ml, KBE/ml)
For Ozone water treatment application, stainless steel 316L execution is required.
Model
DFCV-EC9122-*
DFCV-EC9123-*
DFCV-EC9124-*
DFCV-EC9125-*
DFCV-EC9126-*
DFCV-EC9127-*
If any of the following happens:
at ambient conditions exceeding the given maximum ambient conditions,
with supply water quality data exceeding one or more of the concentration limits of above table "Minimum
supply water quality",
if the supply water has a Practical Scaling Index below 5.5,
Then:
the water flow needs to be increased to higher levels to avoid rapid fouling and scaling of the pre-cooler
medium. Contact your local BAC-Balticare representative for support.
3 Water care
3 Water care
Minimum supply water quality
Number of fans
4 fans
6 fans
8 fans
10 fans
12 fans
14 fans
Recommended adiabatic pre-cooler water flow rates
Baltiplus 800™ coating
< 20 ºC
6.5 – 9
50 – 500 mg/l
< 500 mg/l
< 1500 mg/l
< 200 mg/l
< 250 mg/l
1800 µS/cm
< 1000
Minimum pre-cooler water flow
per unit
14 l/min
22 l/min
28 l/min
36 l/min
44 l/min
50 l/min