Bus there are no stations possible which station number is greater than 127. (FC=YYh)
ErrCode 02: At state-protocol the Source-Address is detected as 127. This is the Broadcast-address
which is not possible.
ErrCode 03: The received State protocols destination address (XXX respectively YYY) does not exist
in the MPI-Bus. (FC=ZZh)
ErrCode 04: The function-code (YYh) of the received State protocol from XXX is incorrect. The 7th Bit
is High, but according to the specification the Bit has to be low.
ErrCode 05: A State protocol has been received. But the function-code (YYh) means that the
participant is not ready to enter the bus.
ErrCode 06: The function-code in the State-protocol received from XXX is unknown (FC=YYh)
ErrCode 11: The sender (XXX) of the received data-protocol is unknown. To send data the participant
must get the Token. (SSAP=YYh, FC=ZZh, length=UUU)
ErrCode 12: Data-protocol with Source-address 255 (Broadcast) is useless. (CPU=XXX, SSAP=YYh,
FC=ZZh, length=UUU)
ErrCode 13: The sender (XXX) of the received data-protocol is unknown. To send data the participant
must get the Token. (SSAP=YYh, FC=ZZh, length=UUU)
ErrCode 14: The 7th Bit of the function-code is High, but according to the specification the Bit has to
be low. (CPU=XXX, SSAP=YYh, FC=ZZh, length=UUU)
ErrCode 15: The upper 4 Bit of the Function-code are wrong/unknown)
(CPU=XXX, SSAP=YYh, FC=ZZh, length=UUU)
ErrCode 16: Unknown function-code has been transmitted to the cable. (CPU=XXX, SSAP=YYh,
FC=ZZh, length=UUU)
ErrCode 17: Destination-SAP are defined till 3Fh in data-protocols. (CPU=XXX, SSAP=YYh, FC=ZZh,
length=UUU)
ErrCode 18: Source-SAP are defined till 3Fh in data-protocols. (CPU=XXX, SSAP=YYh, FC=ZZh,
length=UUU)
ErrCode 19: Received a data-protocol with destination-SAP=0, Connection request from another bus-
participant with our cable. (CPU=XXX,SSAP=YYh,FC=ZZh,DSAP=UUh)
ErrCode 1A: Participants are sending data to our cable with source-SAP = 0, which means that the
participant has not made a connection establishment or has lost the negotiated SAP.
(CPU=XXX,SSAP=YYh,FC=ZZh,DSAP=UUh)
ErrCode 1B: Data-protocol with unknown data-function-code received.
(CPU=XXX,SSAP=YYh,FC=ZZh,DFC=UUh)
ErrCode 1C Data-protocol with unknown data-function-code received.
(CPU=XXX,SSAP=YYh,FC=ZZh,DFC=UUh)
ErrCode 1D: Received a state-protocol with error-code.
(CPU=XXX,FPGA=YYh,RAM=ZZh)
ErrCode 1E: FPGA has caused an interrupt although no data present.
(SD1=XXh,SD1=YYh,CPU=ZZZ,FC=UUh)
ErrCode 20: Unknown protocol at PPIMultimaster-Mode. (FC=XXh,Länge=YYY)
ErrCode 21: Unknown baud-rate at PPIMultimaster-Mode. (Baudrate=XXh) After that additional hints
are displayed.
SMS:
SMS: Switches Processing OFF / Only Receive / Only Send / Receive and Send.
Attention: before setting ON check configuration, after activating the device will go into the MPI-BUS and
tries to connect to the defined PLC. Receive of SMS only with TELESERVICE-GSM Receive of DTMF only with
with TELESERVICE GSM
TS: local station-address (should not be used twice in the MPI/Profibus!)