Electrical Specifications (60Hz) - Daikin FXSQ25MVE9 Technical Data Manual

Concealed ceiling unit
Table of Contents

Advertisement

1
Specifications

1-3 Electrical Specifications (60Hz)

Power Supply
Name
Phase
Frequency
Voltage
Current
Minimum circuit amps (MCA)
Maximum fuse amps (MFA)
Full load amps (FLA)
Voltage range
Minimum
Maximum
Notes
1-3 Electrical Specifications (60Hz)
Power Supply
Name
Phase
Frequency
Voltage
Current
Minimum circuit amps (MCA)
Maximum fuse amps (MFA)
Full load amps (FLA)
Voltage range
Minimum
Maximum
Notes
• Indoor Units • Concealed Ceiling Unit • FXSQ-MVE9
FXSQ20MVE9
Hz
V
A
A
A
V
V
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
Hz
V
A
A
A
V
V
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
®
• VRV
Systems • Indoor Units
FXSQ25MVE9
FXSQ32MVE9
0.6
0.6
0.8
15
15
15
0.5
0.5
0.6
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
FXSQ80MVE9
FXSQ100MVE9
1.8
15
1.4
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
FXSQ40MVE9
FXSQ50MVE9
VE
1~
60
220
0.9
1.0
15
15
0.7
0.8
-10%
+10%
FXSQ125MVE9
VE
1~
60
220
1.9
2.5
15
15
1.5
2.0
-10%
+10%
3
FXSQ63MVE9
1
1
1.4
15
1.1
5