Daikin FXSQ25MVE9 Technical Data Manual page 9

Concealed ceiling unit
Table of Contents

Advertisement

4
Capacity tables
4 - 1 Cooling capacity tables
FXSQ-M
Outdoor
Nominal
Unit size
air temp.
capacity
1
°CDB
50
5.6
10.0
12.0
14.0
4
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
42.0
44.0
46.0
63
7.1
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
42.0
44.0
46.0
80
9.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
42.0
44.0
46.0
10.0
100
11.2
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
42.0
44.0
46.0
10.0
125
14.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
42.0
44.0
46.0
8
• Indoor Units • Concealed Ceiling Unit • FXSQ-MVE9
14.0°CWB
16.0°CWB
20.0°CDB
23.0°CDB
TC
SHC
TC
SHC
3.8
3.2
4.5
3.7
3.8
3.2
4.5
3.7
3.8
3.2
4.5
3.7
3.8
3.2
4.5
3.7
3.8
3.2
4.5
3.7
3.8
3.2
4.5
3.7
3.8
3.2
4.5
3.7
3.8
3.2
4.5
3.7
3.8
3.2
4.5
3.7
3.8
3.2
4.5
3.7
3.8
3.2
4.5
3.7
3.8
3.2
4.5
3.7
3.8
3.2
4.5
3.7
3.8
3.2
4.5
3.7
3.8
3.2
4.5
3.7
3.8
3.2
4.5
3.7
3.8
3.1
4.5
3.5
3.8
3.1
4.5
3.5
3.8
3.1
4.5
3.5
4.8
4.1
5.7
4.8
4.8
4.1
5.7
4.8
4.8
4.1
5.7
4.8
4.8
4.1
5.7
4.8
4.8
4.1
5.7
4.8
4.8
4.1
5.7
4.8
4.8
4.1
5.7
4.8
4.8
4.1
5.7
4.8
4.8
4.1
5.7
4.8
4.8
4.1
5.7
4.8
4.8
4.1
5.7
4.8
4.8
4.1
5.7
4.8
4.8
4.1
5.7
4.8
4.8
4.1
5.7
4.8
4.8
4.1
5.7
4.8
4.8
4.1
5.7
4.8
4.8
4.1
5.7
4.7
4.8
4.1
5.7
4.7
4.8
4.1
5.7
4.7
6.1
5.0
7.2
5.7
6.1
5.0
7.2
5.7
6.1
5.0
7.2
5.7
6.1
5.0
7.2
5.7
6.1
5.0
7.2
5.7
6.1
5.0
7.2
5.7
6.1
5.0
7.2
5.7
6.1
5.0
7.2
5.7
6.1
5.0
7.2
5.7
6.1
5.0
7.2
5.7
6.1
5.0
7.2
5.7
6.1
5.0
7.2
5.7
6.1
5.0
7.2
5.7
6.1
5.0
7.2
5.7
6.1
5.0
7.2
5.7
6.1
5.0
7.2
5.7
6.1
5.0
7.2
5.8
6.1
5.0
7.2
5.8
6.1
5.0
7.2
5.8
7.6
6.2
9.0
7.2
7.6
6.2
9.0
7.2
7.6
6.2
9.0
7.2
7.6
6.2
9.0
7.2
7.6
6.2
9.0
7.2
7.6
6.2
9.0
7.2
7.6
6.2
9.0
7.2
7.6
6.2
9.0
7.2
7.6
6.2
9.0
7.2
7.6
6.2
9.0
7.2
7.6
6.2
9.0
7.2
7.6
6.2
9.0
7.2
7.6
6.2
9.0
7.2
7.6
6.2
9.0
7.2
7.6
6.2
9.0
7.2
7.6
6.2
9.0
7.2
7.6
6.2
9.0
7.1
7.6
6.2
9.0
7.1
7.6
6.2
9.0
7.1
9.4
7.8
11.3
9.0
9.4
7.8
11.3
9.0
9.4
7.8
11.3
9.0
9.4
7.8
11.3
9.0
9.4
7.8
11.3
9.0
9.4
7.8
11.3
9.0
9.4
7.8
11.3
9.0
9.4
7.8
11.3
9.0
9.4
7.8
11.3
9.0
9.4
7.8
11.3
9.0
9.4
7.8
11.3
9.0
9.4
7.8
11.3
9.0
9.4
7.8
11.3
9.0
9.4
7.8
11.3
9.0
9.4
7.8
11.3
9.0
9.4
7.8
11.3
9.0
9.4
7.8
11.3
9.0
9.4
7.8
11.3
9.0
9.4
7.8
11.3
9.0
®
• VRV
Systems • Indoor Units
Indoor air temperature
18.0°CWB
19.0°CWB
26.0°CDB
27.0°CDB
TC
SHC
TC
SHC
5.2
3.9
5.6
4.1
5.2
3.9
5.6
4.1
5.2
3.9
5.6
4.1
5.2
3.9
5.6
4.1
5.2
3.9
5.6
4.1
5.2
3.9
5.6
4.1
5.2
3.9
5.6
4.1
5.2
3.9
5.6
4.1
5.2
3.9
5.6
4.1
5.2
3.9
5.6
4.1
5.2
3.9
5.6
4.1
5.2
3.9
5.6
4.1
5.2
3.9
5.6
4.1
5.2
3.9
5.6
4.1
5.2
3.9
5.5
4.0
5.2
3.9
5.4
3.9
5.2
3.7
5.3
3.7
5.1
3.7
5.2
3.7
4.8
3.4
4.8
3.4
6.6
4.9
7.1
5.2
6.6
4.9
7.1
5.2
6.6
4.9
7.1
5.2
6.6
4.9
7.1
5.2
6.6
4.9
7.1
5.2
6.6
4.9
7.1
5.2
6.6
4.9
7.1
5.2
6.6
4.9
7.1
5.2
6.6
4.9
7.1
5.2
6.6
4.9
7.1
5.2
6.6
4.9
7.1
5.2
6.6
4.9
7.1
5.2
6.6
4.9
7.1
5.2
6.6
4.9
7.1
5.2
6.6
4.9
7.0
5.2
6.6
4.9
6.9
5.1
6.6
4.8
6.7
4.9
6.5
4.7
6.6
4.9
6.1
4.5
6.1
4.5
8.4
6.1
9.0
6.3
8.4
6.1
9.0
6.3
8.4
6.1
9.0
6.3
8.4
6.1
9.0
6.3
8.4
6.1
9.0
6.3
8.4
6.1
9.0
6.3
8.4
6.1
9.0
6.3
8.4
6.1
9.0
6.3
8.4
6.1
9.0
6.3
8.4
6.1
9.0
6.3
8.4
6.1
9.0
6.3
8.4
6.1
9.0
6.3
8.4
6.1
9.0
6.3
8.4
6.1
9.0
6.3
8.4
6.1
8.9
6.2
8.4
6.1
8.7
6.2
8.4
6.1
8.5
6.1
8.2
6.0
8.3
6.0
7.7
5.6
7.7
5.5
10.5
7.6
11.2
7.9
10.5
7.6
11.2
7.9
10.5
7.6
11.2
7.9
10.5
7.6
11.2
7.9
10.5
7.6
11.2
7.9
10.5
7.6
11.2
7.9
10.5
7.6
11.2
7.9
10.5
7.6
11.2
7.9
10.5
7.6
11.2
7.9
10.5
7.6
11.2
7.9
10.5
7.6
11.2
7.9
10.5
7.6
11.2
7.9
10.5
7.6
11.2
7.9
10.5
7.6
11.2
7.9
10.5
7.6
11.0
7.7
10.5
7.6
10.8
7.7
10.4
7.5
10.6
7.5
10.2
7.4
10.4
7.4
9.6
7.0
9.6
6.8
13.1
9.6
14.0
9.9
13.1
9.6
14.0
9.9
13.1
9.6
14.0
9.9
13.1
9.6
14.0
9.9
13.1
9.6
14.0
9.9
13.1
9.6
14.0
9.9
13.1
9.6
14.0
9.9
13.1
9.6
14.0
9.9
13.1
9.6
14.0
9.9
13.1
9.6
14.0
9.9
13.1
9.6
14.0
9.9
13.1
9.6
14.0
9.9
13.1
9.6
14.0
9.9
13.1
9.6
14.0
9.9
13.1
9.6
13.8
9.8
13.1
9.6
13.5
9.6
13.0
9.5
13.2
9.3
12.8
9.3
13.0
9.2
12.0
8.7
12.1
8.5
TC: Total Capacity;kW - SHC: Sensible capacity; kW
20.0°CWB
22.0°CWB
28.0°CDB
30.0°CDB
TC
SHC
TC
SHC
6.0
4.3
6.7
4.0
6.0
4.3
6.7
4.0
6.0
4.3
6.7
4.0
6.0
4.3
6.7
4.0
6.0
4.3
6.6
3.9
6.0
4.3
6.5
3.9
6.0
4.3
6.4
3.9
6.0
4.3
6.4
3.8
6.0
4.3
6.3
3.8
6.0
4.3
6.2
3.8
5.9
4.3
6.1
3.7
5.9
4.3
6.0
3.7
5.8
4.2
5.9
3.7
5.7
4.2
5.8
3.6
5.6
4.1
5.7
3.6
5.5
4.1
5.6
3.6
5.3
3.8
5.5
3.7
5.3
3.7
5.4
3.6
4.8
3.4
4.8
3.2
7.6
5.5
8.5
5.6
7.6
5.5
8.5
5.6
7.6
5.5
8.5
5.6
7.6
5.5
8.5
5.6
7.6
5.5
8.3
5.5
7.6
5.5
8.2
5.4
7.6
5.5
8.2
5.4
7.6
5.5
8.1
5.3
7.6
5.5
7.9
5.2
7.6
5.5
7.8
5.2
7.5
5.5
7.7
5.1
7.4
5.4
7.6
5.1
7.3
5.3
7.5
5.0
7.2
5.2
7.4
5.0
7.1
5.2
7.2
5.0
7.0
5.2
7.1
4.9
6.8
5.0
7.0
4.9
6.7
4.9
6.8
4.8
6.1
4.5
6.1
4.3
9.6
6.7
10.8
6.8
9.6
6.7
10.8
6.8
9.6
6.7
10.8
6.8
9.6
6.7
10.7
6.8
9.6
6.7
10.6
6.7
9.6
6.7
10.4
6.6
9.6
6.7
10.4
6.6
9.6
6.7
10.2
6.5
9.6
6.7
10.1
6.4
9.6
6.7
9.9
6.3
9.5
6.6
9.8
6.2
9.4
6.5
9.6
6.2
9.3
6.4
9.5
6.1
9.1
6.3
9.3
6.1
9.0
6.3
9.2
6.0
8.8
6.3
9.0
6.0
8.6
6.1
8.8
5.8
8.5
6.0
8.7
5.7
7.8
5.5
7.8
5.1
11.9
8.3
13.4
8.5
11.9
8.3
13.4
8.5
11.9
8.3
13.4
8.5
11.9
8.3
13.3
8.4
11.9
8.3
13.2
8.3
11.9
8.3
13.0
8.2
11.9
8.3
12.9
8.2
11.9
8.3
12.7
8.0
11.9
8.3
12.5
7.9
11.9
8.3
12.3
7.8
11.9
8.2
12.2
7.7
11.7
8.1
12.0
7.7
11.5
8.0
11.8
7.6
11.3
7.9
11.6
7.5
11.2
7.8
11.4
7.5
11.0
7.8
11.2
7.4
10.7
7.6
11.0
7.2
10.5
7.4
10.8
7.1
9.7
6.8
9.7
6.4
14.9
10.3
16.7
10.7
14.9
10.3
16.7
10.7
14.9
10.3
16.7
10.7
14.9
10.3
16.7
10.7
14.9
10.3
16.4
10.5
14.9
10.3
16.2
10.4
14.9
10.3
16.1
10.3
14.9
10.3
15.9
10.2
14.9
10.3
15.6
10.0
14.9
10.3
15.4
9.9
14.9
10.3
15.2
9.8
14.6
10.1
15.0
9.7
14.4
10.0
14.7
9.6
14.2
9.8
14.5
9.4
13.9
9.7
14.3
9.3
13.7
9.6
14.1
9.2
13.4
9.5
13.7
9.0
13.1
9.3
13.5
8.8
12.1
8.6
12.1
7.9
24.0°CWB
32.0°CDB
TC
SHC
7.1
4.2
7.0
4.2
6.9
4.2
6.8
4.1
6.7
4.1
6.6
4.1
6.6
4.0
6.5
4.0
6.4
4.0
6.3
3.9
6.2
3.9
6.1
3.8
6.0
3.8
5.9
3.8
5.8
3.7
5.8
3.7
5.6
3.4
5.5
3.4
4.9
3.0
9.0
5.4
8.9
5.3
8.7
5.3
8.6
5.2
8.5
5.1
8.4
5.1
8.3
5.0
8.2
5.0
8.1
4.9
8.0
4.9
7.9
4.9
7.8
4.8
7.6
4.8
7.5
4.8
7.4
4.7
7.3
4.7
7.1
4.6
7.0
4.5
6.2
4.0
11.4
6.6
11.2
6.5
11.1
6.4
10.9
6.3
10.8
6.3
10.6
6.2
10.6
6.1
10.4
6.0
10.3
6.0
10.1
5.9
10.0
5.9
9.8
5.8
9.7
5.8
9.5
5.8
9.4
5.7
9.3
5.7
9.0
5.6
8.9
5.5
7.8
4.8
14.2
8.2
14.0
8.1
13.8
8.0
13.6
7.9
13.4
7.8
13.2
7.7
13.2
7.6
13.0
7.5
12.8
7.5
12.6
7.4
12.4
7.3
12.2
7.3
12.1
7.3
11.9
7.2
11.7
7.1
11.5
7.1
11.2
6.9
11.1
6.8
9.7
6.0
17.7
10.6
17.5
10.4
17.2
10.3
17.0
10.2
16.8
10.0
16.6
9.9
16.4
9.8
16.2
9.7
16.0
9.6
15.8
9.5
15.5
9.4
15.3
9.3
15.1
9.2
14.9
9.1
14.6
8.9
14.4
8.9
14.1
8.7
13.8
8.5
12.2
7.5
CA05A396