21.2 Main Board Option Settings

All monitor option jumpers for the Dual Vibration Monitor are on the Main Board. The
following table lists these options and their jumper positions.
Option Settings on Newer Version of the Main Board (Part Number 140720-01)
OPTION
First Out
Alert Mode
Danger Mode
Danger Voting
Danger Bypass Switch
Vibration Alarm Delay **
Gap Alarm
Recorder Clamping Mode
+4 to 20 mA Rec. only
Corner Frequency Option
* Standard configuration as shipped from factory.
** Gap Alarm Delay is 6 s.
Section 21 - Appendix A – Monitor Options for PWA 140720-01
SETTING
Enabled *
Disabled
Latching *
Nonlatching
Latching *
Nonlatching
And Relay Drive
Or Relay Drive *
Enabled
Disabled *
0.1 s.
1 s.
3 s. *
6 s.
Enabled
Disabled *
NOT OK = 4 mA
NOT OK = 2 mA*
60-36,000 RPM
240-240,000 RPM*
JUMPER
INSTALL
REMOVE
----------
W20I
W20I
----------
----------
W20G
W20G
----------
----------
W20F
W20F
----------
W20H
----------
----------
W20H
W20C
----------
----------
W20C
W20A
W20B
W20A,B
----------
----------
W20A,B
W20B
W20A
W20D
----------
----------
W20D
----------
W17E, F
----------
W17E, F
W15B, C,
W15A, D,
W16E-H, M-P
W16A-D, I-L
W15A, D,
W15B, C,
W16A-D, I-L
W16E-H, M-P