5. Reduce the gap voltage to read below the Over Gap setpoint (and above the Under Gap
Setpoint) and observe that the ALERT LED goes off (if the nonlatching alarm jumper is
installed). Press the RESET switch on the System Monitor to reset latching alarms.
6. Repeat section 15.3 for under Gap alarms, adjusting the gap signal to be below the
Under Gap Alert setpoint.

15.4 Channel B and Reinstallation

1. Reconnect the wiring to the Signal Input Relay Module that was discussed in section
15.1.
2. Repeat sections 15.1 through 15.3 connecting the multimeter and function generator to
the channel B terminals.
3. If the Channel Bypass or Danger Bypass functions were activated for this procedure,
deactivate them by setting the appropriate switches (BA, BB, or DB) to the right (OFF).