Tx-I/O Module Feature Summary - Siemens TALON Series Technical Reference Manual

Tx-i/o modules and island bus
Table of Contents

Advertisement

TX-I/O Module Feature Summary

Function
General
Local Override
LCD Display
AI
NI 1000 LS
PT 1000 385
LT 1000 375
NTC 10K (w/out diode)
NTC 100K
0-10 Vdc
4-20 mA
AO
0-10 Vdc
4-20 mA
DI
Static Contact (NC/NO)
Pulse accumulator
25 Hz Counter (with debouncing)
10 Hz Counter (with debouncing)
DO
ON/OFF
Pulse ON
4-20 mA functionality is available only point terminations 5-8
1)
10 Hz counter functionality is available only on point terminations 1-8
2)
Siemens Industry, Inc.
588-587
CAUTION
Active inputs and output are permitted on the same module when connected
sensors are powered from that module.
When sensors are externally powered, active inputs and outputs should be on
separate modules.
TX-I/O Module Product Number and Name
TXM1.
8X-ML
8 Super
Universal
1
CONFIDENTIAL: For internal use only
TXM1.
TXM1.
TXM1.
8X
8U-ML
8U
8 Universal
1
TALON TX-I/O Modules and Island Bus Technical Reference
TX-I/O Modules
TXM1.
TXM1.
TXM1.
8D
16D
6R-M
8 DI
16 DI
6 DO Relay
2