Supply Terminal Connections; Active Input And Output Support - Siemens TALON Series Technical Reference Manual

Tx-i/o modules and island bus
Table of Contents

Advertisement

Supply Terminal Connections

Active Input and Output Support

Siemens Industry, Inc.
588-587
NOTE:
The neutral of analog inputs and outputs must always be connected to the
terminal associated with that I/O input.
All supply terminals are connected in the I/O module, not in the terminal base.
The neutral of a digital input (on Digital Input, Universal and Super Universal
modules) can be connected to any neutral terminal on the same module. Several
digital inputs can also share a neutral terminal on the same module.
DC Output (Field Supply)
The following information applies to terminals 3, 11, 20, and 28.
Nominal voltage (derived in the module from
the module supply voltage)
Admissable current per module
AC/DC Output (Field Supply)
The following information applies to terminals 7, 15, 24, and 32.
Voltage
Admissable current per module
Fuse
CAUTION
Active inputs and output are permitted on the same module when connected
sensors are powered from that module.
When sensors are externally powered, active inputs and outputs should be on
separate modules.
NOTE:
The neutral of analog inputs and outputs must always be connected to the
terminal associated with that I/O input.
Active input and output support includes the following:
Analog input and output (0-10 Vdc)
Analog input current 4-20 mA
Analog output current 4-20 mA (four current outputs maximum per module on
Points 5 through 8)
24 Vdc supply voltage for sensors at a maximum of 200 mA per module.
CONFIDENTIAL: For internal use only
24 Vdc
Max. 200 mA (total for all four terminals)
AC/DC 12 to 24 V
Max. 4 A (total for all four terminals)
4A, in TX-I/O Power Supply or
Bus Connection Module
TALON TX-I/O Modules and Island Bus Technical Reference
TX-I/O Modules
25
4/6/2010