Siemens TALON Series Technical Reference Manual page 12

Tx-i/o modules and island bus
Table of Contents

Advertisement

TX-I/O Modules
Function
General
Intrinsic consumption
Unconfigured I/O point
(Reserve for later configuration)
AI
Temperature sensors Ni, PT
Temperature sensor NTC
Resistance
3)
10 Vdc
2)
20 mA, Supply external or 24 Vac
20 mA, 2-wire
2)
20 mA, 3-wire
2) 4)
AO
10 Vdc
2)
20 mA
2)
DI
Contact closed
2)
DO
Relay, contact closed
Including module status LED; includes LCD and all override LEDs if applicable.
1)
Including I/O status LED.
2)
Included in intrinsic consumption (no I/O status LED for temperature inputs).
3)
The table assumes 5 mA to supply the current sensor, which should be sufficient for most models. If in doubt, please refer to the
4)
sensor data sheet.
12
Siemens Industry, Inc.
588-587
NOTE:
The 24 Vdc consumption from the modules of field devices other than current
sensors must be counted separately. Admissible current for each TXM1.8X or
TXM1.8X-ML module: 200 mA.
TX-I/O Module Consumption Data
(24 Vdc per I/O point, values in mA for supply sizing)
TXM1.
8X-ML
8 Super
Universal
35
1)
25
0
3)
0
3)
0.5
0.5
0.5
2)
20
25
2.5
18
2
2)
CONFIDENTIAL: For internal use only
TXM1.
TXM1.
TXM1.
TXM1.
8X
8U-ML
8U
8D
8 Universal
30
60
35
25
3
3
0
0
0
0
0
0
0.5
1
1
0.5
1
1
0.5
20
25
2.5
3
3
18
2
3
3
TALON TX-I/O Modules and Island Bus Technical Reference
TXM1.
TXM1.
TXM1.
16D
6R-M
6R
8 DI
16 DI
6 DO Relay
25
25
30
3.5
2.5
8
3.5
2.5
8
4/6/2010
20
8
8

Advertisement

Table of Contents
loading

Table of Contents