Eaton CM52 Instruction Leaflet page 7

Network protector with arc flash reduction module
Hide thumbs Also See for CM52:

Advertisement

CM52 Network Protector
with Arc Flash Reduction Module
Figure 11. Wiring Harness Connections
Re-install the Upper Interphase Barrier Assembly.
StEP 12
Route the new harness beside the original secondary harness and
wire tie the new harness to the original harness starting from the
top and working downward . Note, leave a small loop around the 28
pt plug/socket bracket . Cut the free ends of the wire ties off with a
pair of side cutters
StEP 13
Using the photo in Figure 12 for location and proper orientation,
attach the Ground Alarm Power Supply Module (GAPs module) to
the inside left hand side sheet of the relay module by removing the
protective paper covering the adhesive strips .
Figure 12. Location of the GAPs Module
Instruction Leaflet IL02401001E
StEP 14
Connect the four point twist connector from the new secondary har-
ness to its mate on the GAPs module .
From the six pin connector mounted on the GAPs module, the wire
marked GRD should be located facing toward the roof sheet of the
relay module . Connect the GRD wire to the ground point on the rear
sheet of the relay module as shown of Figure 12 . Referring to Figure
13, connect the 120 V lead to the second point from the left (front
side) on the gray Phoenix terminal block . Note, you will end up with
two wires at the terminal point marked L1 . There will be two free fly-
ing leads marked I3 and I3A as part of the secondary harness which
are used for a hard wired ON-OFF switch .
Figure 13. Connection of the 120 V Lead to the Phoenix Terminal
Block.
EAtoN CoRPoRAtIoN www.networkprotectors.net
Effective August 2009
7