Instruction Leaflet IL02401001E
Effective August 2009
7.0 ARM-IDM Retro-fit Field Installation
Instructions
Please review the instruction sheet and fully understand the compo-
nent placement prior to installation .
D
C
B
Figure 2. Components of the ARM-IDM Retro-fit Kit
Components in Kit
A. CM52 ARM-IDM
B. ARM Ct Module
C. Ground Alarm Power Supply Module (GAPSm)
D. Secondary Harness to Relay Module
− 3 Wire Harness- CM52 ARM-IDM to R/H Secondary Block
− 9 Wire Harness w/ IDM connector to L/H Secondary Block
− 10 ft (3.05 m)of AWG #16 teflon wire, wire ties and butt
splices (not shown)
Tools Required (Not Supplied with Kit)
Small screwdriver with 1/8" (3 mm) wide blade
Screwdriver with 1/4" (6 mm) wide blade
#2 Phillips head screwdriver
7/16" wrench
Wire cutters
Wire stripper
Wire connector crimp tool
AMPE pin extraction tool #305183-R
(AMP is a Registered Trademark of TYCO International, LTD .)
4
EAtoN CoRPoRAtIoN www.networkprotectors.net
A
with Arc Flash Reduction Module
Installation Instruction
Note The ARM-IDM Retro-fit Kit will only function on those CM52 break-
ers which utilize the Indicating Diagnostic Module (IDM) . This kit cannot
be applied to the first generation CM52 using the Voltage Regulator Device
(VRD) as the breaker wiring is different from that of current production .
Installation of this kit should take approximately 2 .5 hours . Please refer to
your supplied wiring diagram as certain component add-ons can change
the configuration of the relay module . For help, please contact EATON,
Greenwood, SC (PH- 864-942-6211) .
For ease of wiring to INCOM or any connections to be made outside of the
network housing, it is suggested that you use the Bulkhead Entry Box, style
number NFX0012G01 .
StEP 1
Following all safety guidelines, open the network breaker and place
it in the drawn out and disconnected position .
 Warning
ensure that the breaker is de-energized prior to proceeding.
StEP 2
Remove the front cover of the CM52 breaker using the 10 mm
socket supplied with the lever-out crank . Loosen the four cover bolts;
they should be captive to the front cover .
Note: Pull the manual closing handle completely forward to facilitate the
removal of the front cover .
StEP 3
Remove the existing IDM by opening the cover on the right center
of the IDM and removing the screw . Pull the IDM straight out from
the breaker to avoid bending any of the contact pins .
StEP 4
Remove the mounting plate which supports the IDM . There are four
Phillips head screws that hold this plate in position .
Figure 3. Location of the Screws to Be Removed
CM52 Network Protector