6 How to Program
27-92 Current % of Total Capacity
Current % of Total Capacity is a readout parameter that shows the system operating point as a % capacity of total system capacity. 100% means all
pumps are on at full speed.
Units: %
27-93 Cascade Option Status
Option:
[0] *
Disabled
Off
Running
Running at FSBW
Jogging
In Open-loop
Frozen
6
Emergency
Alarm
Staging
De-staging
Alternating
Lead Pump Not Set
6-12
Function:
Cascade Option Status is a readout parameter to show the status of the cascade system.
The cascade option is not used.
The cascade option is turned off.
The cascade option is running normally.
The cascade option is running in fixed speed mode. No variable speed pumps are available.
The system is running at the jog speed set in P3-11.
The system is set to open-loop.
The system is frozen in the current state. No changes will take place.
The system has stopped due to Coast, Safety Interlock, Trip Lock, or Safe Stop.
The system is operating with an alarm condition.
A staging operation is in progress.
A de-staging operation is in progress.
An alternation operation is in progress.
A lead pump has not been selected.
®
MI.38.C2.22 - VLT
is a registered Danfoss trademark
Extended and Advanced Cascade Controller
Option