Specifications - Carrier Equipment Touch Installation And Setup Manual

Hide thumbs Also See for Equipment Touch:
Table of Contents

Advertisement

What is the Equipment Touch?
You wire the Equipment Touch to the controller's Rnet port. The Equipment Touch must be powered by an external
power source. The Rnet can have one Equipment Touch, plus ZS sensors and/or a Wireless Adapter that
communicates with wireless sensors.
NOTE The Equipment Touch cannot share the Rnet with SPT Sensors or a TruVu™ ET Display.
You can install and run the Equipment Touch with only its built-in system screens, or you can create a customized
touchscreen file in ViewBuilder. This requires that you:
1
Create customs screens in ViewBuilder, and then save the touchscreen (.touch) file. See "Working with
touchscreens" in ViewBuilder Help.
2
In the i-Vu® interface, right-click the controller and select Driver Properties to attach the touchscreen file.
3
Download All Content to the controller. See "Downloading to controllers" in i-Vu® Help.

Specifications

Power
Display
Enclosure
Ports
Microcontroller
Memory
Real-time clock
Audible alarm
notification
Temperature sensor
Humidity sensor
Environmental
operating range
Mounting
Equipment Touch
Installation and Setup Guide
Requires a 24 Vac (±15%), 5 VA, 50–60 Hz, Class 2 external power supply
4.3 in. resistive touchscreen color LCD display with backlighting (Wide Quarter VGA,
480x272 pixels)
ABS plastic with polycarbonate bezel
EIA-485 based serial port for Rnet communication
USB host port
32-bit
16 MB Flash memory to store program code and screen file.
1.5 MB RAM to store variable data and LCD data.
4 KB Serial EEPROM to store non-volatile configuration data.
A 365-day real time clock/calendar chip. The time and date will be maintained for a
minimum of 72 hours after loss of power (at room temperature).
A piezoelectric sounder
Range:
Accuracy over 30.0°F to 100°F:
Accuracy over full range:
Resolution:
Range:
Accuracy over 20 to 80% RH:
Accuracy over full range:
Resolution:
-4ºF to 140ºF (-20ºC to 60ºC), 10–90% RH, non-condensing
Wall or panel mounting within the building interior.
-4.0°F to 140°F (-20°C to 60°C)
±1.0°F (±0.55°C)
±2.0°F (±1.1°C)
0.2°F (0.1°C)
0 to 100% RH
±3.0% RH
±5.0% RH
0.05% RH
2
CARRIER CORPORATION ©2019
All rights reserved

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents