CAUTION Allow no more than 0.06 inch (1.5 mm) bare communication wire to protrude. If bare
communication wire contacts the cable's foil shield, shield wire, or a metal surface other than the terminal
block, the device may not communicate correctly.
7
Attach the backplate to the wall or panel. If mounting in or on a panel:
a)
Drill two 3/16 inch (4.8 mm) pilot holes in the panel.
b)
Attach backplate using pan head 6-32 x 3/8" to l/2" long machine screws. Do not overtighten screws to
prevent damage to plastic housing.
RECOMMENDATION Use Loctite 220 on screw threads if the Equipment Touch will be subject to
vibration.
8
Attach the Equipment Touch to the backplate:
a)
Place the bottom of the Equipment Touch onto the backplate by aligning the 2 slots on the Equipment
Touch with the tabs on the backplate.
b)
Push the Equipment Touch onto the backplate until the tabs at the top of the Equipment Touch snap
onto the backplate.
9
Turn off the controller's power.
10 Connect the other end of the Rnet wiring to the controller's Rnet port or to a zone sensor.
NOTES
Insert the shield wire with the ground wire into the controller's GND terminal.
Use the same polarity throughout the Rnet.
11 Connect power wiring to a 24 Vac power supply.
12 Turn on the controller's power.
Equipment Touch
Installation and Setup Guide
Wiring and mounting the Equipment Touch
17
CARRIER CORPORATION ©2019