Appendix: External sensor resistance requirements
Temp (°C)
-40
-35
-30
-25
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
Equipment Touch
Installation and Setup Guide
Temp (°F)
Resistance (Ohms)
-40
335,651
-31
242,195
-22
176,683
-13
130,243
-4
96,974
5
72,895
14
55,298
23
42,315
32
32,651
41
25,395
50
19,903
59
15,714
68
12,494
77
10,000
86
8,056
95
6,530
104
5,325
113
4,367
122
3,601
131
2,985
140
2,487
149
2,082
158
1,752