Item
Low battery cut-out voltage. This is the low battery voltage setting which shuts down the inverter. This is
2 9
settable when item 0 5 is set to U S E .
C O v
NOTE : This item shuts down only the inverting function. If this function shuts down due to low battery
2 1. 0
cut-out, the charger, transfer, and other functions will still work, as will the display.
4 2 . 0
Selection range (model TL3024E): 25.0 to 31.5 Vdc
Selection range (model TL5048E): 48.0 to 61.0 Vdc
Equalization function. (See page 28.) Selections: E E N (Equalize enabled), E d S (Equalize disabled).
3 0
Allows equalization to take place automatically. This item is settable when item 0 5 is set to either
E E N
F L d or U S E .
3 1
Equalization charging voltage. This is the setting for equalization once enabled in item 3 0 or item 3 6 .
E v
(See page 28.)
2 9 . 2
Selection range (model TL3024E): 25.0 to 31.5 Vdc
5 8 . 4
Selection range (model TL5048E): 48.0 to 61.0 Vdc
3 3
Equalization time. This timer begins running once item 3 1 is reached. (See page 28.)
6 0
Selection range: 5 to 900 minutes.
3 4
Equalization timeout. The maximum time permitted for equalization. (See page 28.)
1 2 0
Selection range: 5 to 900 minutes.
3 5
Equalization interval. The days between automatic equalization cycles. (See page 28.)
3 0 d
Selection range: 0 to 90 days.
Immediate equalization. The main display reads E q . (See page 28.) Selections: A E N (Enabled),
3 6
A d S (Disabled).
A d S
This is usable when 30 is set to E E N .
If A d S is selected, it will cancel equalization until the next automatic cycle based on item 3 5 .
3 7
Reset
PV accumulation kWh data.
N r t
9 3
Erase data log (all accumulated data). Selections: N r t (Not reset), r S t (Reset).
N r t
Data log storage period. During this period, the Alino logs 1000 status items (voltage readings, etc.) for
9 4
analysis. The resulting data is more general if taken across a wider time period. It is more specific if taken
1 0
across a narrower period. Selection range: 3 to 60 days.
9 5
Time (minute) setting. Selection range: 00 to 59.
n I N
9 6
Time (hour) setting. This product uses a 24-hour clock. Selection range: 00 to 23.
H O U
9 7
Date (day) setting. Selection range: 00 to 31.
d A Y
9 8
Date (month) setting. Selection range: 00 to 12.
N o n
9 9
Date (year) setting. Only two digits are used. Selection range: 17 (2017) to 99 (2099).
y E A
900-0248-01-00 Rev A
Table 5
General Settings
Description
Selections: N r t (Not reset), r S t (Reset).
Operation
33

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for OutBack Power Alino TL Series

This manual is also suitable for:

Tl5048eTl3024e