Installation
AC
Before making any connections, open all disconnect devices on both AC and DC sources.
To install AC connections for this product:
NOTE:
Remove approximately 10 mm (½") of the insulation from all AC wires.
1.
Connect the ground (PE) conductor to terminal A.
2.
Connect the input L (line) and N (neutral) conductors to terminals B and C. Connect the
3.
output L and N conductors to terminals D and E. (Use the cable openings as shown.)
Tighten all connections to the torque values required in Table 2.
4.
A
B
C
16
AC wires should be sized according to Table
Install a circuit breaker between the AC source and the input terminals. It is needed for
overcurrent protection and also as a manual disconnect device. For model ATL3024E,
the size is 32 Aac. For model ATL5048E, it is 50 Aac.
Do not reverse the connections to the A
connections before applying power.
D
E
Figure 10
Table 2
Model
Wire Size
2
ATL3024E
4 mm
(#12 AWG)
ATL5048E
6 mm
2
(#10 AWG)
2.
I
and A
O
terminals. Check all
C
N
C
UT
AC Input and
Output Openings
AC Terminals
AC Conductors
Terminal Torque
1.2 Nm (0.89 in-lb)
1.2 Nm (0.89 in-lb)
900-0248-01-00 Rev A