OutBack Power Alino TL Series Owner's Manual page 32

Power conditioning unit
Table of Contents

Advertisement

Settings
Item
0 3
Acceptable AC (utility) input voltage range. Selections: 90 to 280 Vac (A P L ) or 170 to 280 Vac (U P S ).
A P L
0 5
Battery type. Selections: A G n (AGM), F L d (flooded), U S E (user-defined).
A G n
If U S E is selected, battery charging and low DC cutoff voltages can be set in items 2 6 , 2 7 , and 2 9 .
0 6
Auto restart when overload shutdown occurs. Selections: Disable (L r d ) or Enable (l r e ).
L r d
0 7
Auto restart when over-temperature shutdown occurs. Selections: Disable (t r d ) or Enable (t r e ).
t r d
0 9
Output frequency. Selections: 50 Hz or 60 Hz. This item chooses the inverter's AC output frequency.
5 0
1 0
Output voltage. Selections: 220 Vac, 230 Vac, or 240 Vac. This item chooses the inverter's nominal
2 3 0
AC output voltage.
1 1
Maximum charge current (from the utility grid). Selection range: 2 to 60 Adc.
3 0
If item 0 2 is less than item 1 1 , the setting for 0 2 will be used.
Grid transfer voltage. If Item 0 1 is set to S b U , this function transfers the Alino to use the grid upon
1 2
reaching this low-battery voltage.
2 3 . 0
Selections (model TL3024E): 22.0 Vdc to 25.5 Vdc
4 6 . 0
Selections (model TL5048E): 44.0 Vdc to 51.0 Vdc
Battery transfer setting. If the Alino transferred to use the grid after reaching the voltage in item 1 2, it will
1 3
return to using batteries or PV power upon reaching this high-battery setting.
2 7 . 0
Selections (model TL3024E): F U L (full) to 29.0 Vdc
5 4 . 0
Selections (model TL5048E): F U L (full) to 58.0 Vdc
Charger Source Priority setting. If multiple power sources are available, this item controls which source is
used first to charge the batteries. This item can be set to change depending on time of day. (See page 37.)
Selections: C S O , S N U , O S O .
1 6
C S O (charge solar) uses PV as first priority. Utility is used only if PV is not available.
S N U
S N U (solar and utility) charges with both sources as available.
O S O (only solar) charges only with PV, regardless of utility.
1 8
Alarm control. Selections: b O F (alarm off), b O N (alarm on). Turns audible alarm on or off (see page 23).
b O F
When enabled, this alarm causes the unit to beep due to item 22 or when a fault occurs. (See page 39.)
1 9
Return to default display. Selections: E S P (auto return), r E P (remain). Sets the screen to return to the
E S P
default display after 1 minute if no button is pressed, or to remain on the current screen.
2 0
Backlight control. Selections: L O N (Light on), L O F (Light off). Turns the display backlight on or off.
L O N
2 2
Unit beeps when the primary source (according to item 0 1) is interrupted.
A O N
Selections: A O N (Alarm on), A O F (Alarm off).
2 3
Overload bypass. Selections: b y d (Bypass disabled), b y E (Bypass enabled). This function operates
b y d
when item 0 1 is set to S b U . If overload shutdown occurs while using batteries, unit switches to the grid.
2 5
Record fault codes. Selections: F E N (Record enabled), F d S (Record disabled).
F E N
2 6
Bulk charging voltage. This is the setting for the main stages of constant-voltage (CV) charging. (See
C v
page 27.) This is settable when item 0 5 is set to U S E .
2 8 . 2
Selection range (model TL3024E): 25.0 to 31.5 Vdc
5 6 . 4
Selection range (model TL5048E): 48.0 to 61.0 Vdc
2 7
Float charging voltage. This is the setting for the float stage of charging. (See page 27.) This is settable
F L v
when item 0 5 is set to U S E .
5 7 . 0
Selection range (model TL3024E): 25.0 to 31.5 Vdc
5 4 . 0
Selection range (model TL5048E): 48.0 to 61.0 Vdc
32
Table 5
General Settings
Description
900-0248-01-00 Rev A