Multiple Choice Settings Via Modbus - WEG MMW03-M22CH User Manual

Energy analyzer
Table of Contents

Advertisement

4.2 MULTIPLE CHOICE SETTINGS VIA MODBUS

Modbus addresses for the multiple choice settings, input values and their descriptions are given below.
Adress
Register name
538
Connection Type
540
Relay 1 Function
542
Relay 2 Function
546
Password Enable
552
Baud Rate
556
Party Control
Digital Input 1
558
Type
Sayısal Giriş 1
562
Edge
Sayısal Giriş 1
564
Edge
Digital Input 2
568
Edge
Description
Write value
name
0
3P4W
1
3P3W
0
OFF
1
LOW
2
HIGH
0
OFF
1
LOW
2
HIGH
0
OFF
1
ON
0
1200 baud
1
2400 baud
2
4800 baud
3
9600 baud
4
19200 baud
5
38400 baud
6
57600 baud
0
NONE
1
EVEN
2
ODD
0
OFF
1
TARIFF 2
2
COUNTER
3
RUN HOUR
0
RISING
1
FALLING
2
BOTH EDG
0
OFF
1
TARIFF 2
2
COUNTER
3
RUN HOUR
0
RISING
1
FALLING
2
BOTH EDG
Tabela 4.3: Description List
Adress
Register name
Pulse Output 1
570
Parameter
Pulse Output 2
576
Parameter
Menu Scroll On/
582
Of
Home Page
586
Settings
Display
588
Backlights
Options
Energy Analyzer - MMW03-M22CH | 37
www.weg.net
Description
Write value
name
0
OFF
1
IMP ACT1
2
EXP ACT1
3
IMP REA1
4
EXP REA1
5
IMP ACT2
6
EXP ACT2
7
IMP REA2
8
EXP REA2
9
DIN1
10
DIN2
0
OFF
1
IMP ACT1
2
EXP ACT1
3
IMP REA1
4
EXP REA1
5
IMP ACT2
6
EXP ACT2
7
IMP REA2
8
EXP REA2
9
DIN1
10
DIN2
0
OFF
1
ON
0
VOLTAGE (L-N)
1
VOLTAGE (L-L)
2
CURRENT
3
I NEUTR
4
COSQ
5
PF
6
POWER P
7
POWER Q
8
POWER S
9
φ P-Q-S
10
FREQ
11
THD V
12
THD I
0
TIME DEP
1
CONT ON
2
CONT OFF

Advertisement

Table of Contents
loading

Table of Contents