4.1.1 Status/Alarm Flags

"Alarm Flags" modbus address showing the alarm conditions and alarm conditions represented with bits are
given below.
31
30
29
Dl 2
Dl 1
Rel a y 2
Rel a y 2
Status
Status
Status
Status
15
14
13
V2
V1
Freq
Freq
OFF
OFF
Low
High
bit
Description
31
: DI2 Status: Digitial input 2 signal condition (active or passive).
30
: DI1 Status: Digitial input 1 signal condition (active or passive).
29
: DI1 Status: Digitial input 1 signal condition (active or passive).
28
: Relay 1 Status: Relay 1 active/pasive status.
27
: DO2 Status: Digital Output 2 active/pasive status.
26
: DO1 Status: Digital Output 1 active/pasive status.
25-21 : Reserve.
20
: SEQ - Phase Order Alarm.
19
: I3 OFF - 3. No current in Line-3.
18
: I2 OFF - 2. No current in Line-2.
17
: I1 OFF - 1. No current in Line-1.
16
: V3 OFF - 3. No voltage in Line-3.
15
: V2 OFF - 2. No voltage Line-2.
14
: V1 OFF - 1. No voltage in Line-1.
13
: Freq Low - Low frequency alarm.
12
: Freq High - High frequency alarm.
11
: PF Low - Low power factor alarm.
10
: PF High - High power factor alarm.
: Cos φ Low - Low Cos φ alarm.
9
: Cos φ High - High Cos φ alarm.
8
7
: I(N) Low - Low neutral current alarm.
6
: I(N) High - High neutral current alarm.
5
: I Low - Low current alarm.
4
: I High - High current alarm.
3
: V(L-L) Low - Low phase-phase voltage alarm.
2
: V(L-L) High - High phase-phase voltage alarm.
1
: V(L-N) Low - Low phase-neutral voltage alarm.
0
: V(L-N) High - High phase-neutral voltage alarm.
CAUTION!
If the device was not restarted after entering the password or the "password activation time" has not elapsed, this will read
"0" to indicate that password protection is disabled in the "Settings protection" address (modbus adr: 604). In this case,
you don't need to re-enter the password.
Password activation time resets and restarts each time a modbus write action is performed or a key is pressed.
36 | Energy Analyzer - MMW03-M22CH
28
27
26
25
DO2
DO1
Status
Status
12
11
10
9
PF
PF
Cosφ
Low
High
Low
Tabela 4.2: Alarm Flags
458 Alarm Flags
24
23
22
21
Reserve/OFF
8
7
6
Cosφ
I(Nötr)
I(Nötr)
High
Low
High
Low
20
19
18
I3
I2
SEQ
OFF
OFF
5
4
3
2
I
I
V(L-L)
V(L-L)
High
Low
High
17
16
I1
V3
OFF
OFF
1
0
V(L-N)
V(L-N)
Low