Page 1
DB721-CN DB720-CN RS720 LP720 Detector base with loop contact Detector base Detector base seal Detector locking device Meldersockel mit Schlaufkontakt Meldersockel Meldersockel-Dichtung Melderarretierung Installation Montage Building Technologies A6V10213263 Fire Safety & Security Products...
Installation Required space Installation in humid or wet environments The detectors installed must be easily accessible for service and inspection work. It must be possible to remove the detector from directly below using the detector exchanger. The detector base requires a minimum clearance of 2 cm around its sides.
Page 3
Auxiliary terminals Connection diagram, addressed For detector base DB721-CN / DB720-CN – – – – – Connection terminals: 1…2.5 mm Micro terminals: 0.28…0.5 mm Designation plate, detector locking device Control panel Detector base DB721-CN / DB720-CN Connection terminal DBZ1190-XX External alarm indicator...
Montage Platzbedarf Montage in feuchter, nasser Umgebung Für Service- und Revisionsarbeiten müssen die montierten Melder gut zugänglich sein. Die Melder müssen mit dem Pflücker senkrecht von unten herausgenommen werden können. Der Meldersockel muss seitlich min. 2 cm Freiraum haben. * = min. 2 cm Meldersockel-Dichtung RS720 Meldersockel Kabeleinführung...
Page 5
Zusatzklemmen Anschlussschema, adressiert Für Meldersockel DB721-CN / DB720-CN – – – – – Verbindungsklemmen 1…2.5 mm Mikroklemmen 0.28…0.5 mm Melderkennzeichen, Melderarretierung Zentrale Meldersockel DB721-CN / DB720-CN Verbindungsklemme DBZ1190-XX Externer Alarmindikator Melder einsetzen Drehen Sie den Melder (1) im Uhrzeigersinn in den Meldersockel (2) ein.