Legend; Technical Data - Krom Schroder BCU 46 Series Operating Instructions Manual

Burner control unit
Table of Contents

Advertisement

Legend

Ready for operation
Safety interlocks (limits)
High temperature operation
HT
Gas valve
Air valve
Burner
P
Purge
Controlled air flow
Burner operating signal
Start-up signal (BCU)
PZ
Pressure switch for tightness control (TC)
PZH
Pressure switch for maximum pressure
PZL
Pressure switch for minimum pressure
PDZ
Differential pressure switch
P xx Input signal
depending on parameter xx
M
Control element with butterfly valve
TC
Tightness control
p
/2
Half of the inlet pressure
u
p
Outlet pressure
d
GZL
Valve with proof of closure switch
Input/Output, safety circuit
Optional input
xx
Approaching/checking ignition position
Approaching max. capacity
0° 90°
90°
Checking position for max. capacity
I
Current consumption of sensor/contactor
N

Technical data

Ambient conditions
Avoid direct sunlight or radiation from red-hot
surfaces on the unit.
Avoid corrosive influences, e.g. salty ambient air
or SO
.
2
The unit may only be stored/installed in enclosed
rooms/buildings that are not accessible to the
public.
This unit is not suitable for cleaning with a high-
pressure cleaner and/or cleaning products.
Ambient temperature:
-20 to +70°C (-4 to +158°F),
no condensation permitted.
Storage temperature: -20 to +70°C (-4 to +158°F).
Transport temperature = ambient temperature.
Enclosure: IP 65 pursuant to IEC 529.
Safety class: 1.
Pollution degree: internal environment: 2,
external environment: 4.
Permitted operating altitude: < 2000 m AMSL.
Mechanical data
Weight: 5 kg.
Dimensions (W × H × D): 200 × 230 × 135 mm.
Connections:
Screw terminals:
nominal cross-section 2.5 mm²,
wire cross-section (rigid) min. 0.2 mm²,
wire cross-section (rigid) max. 2.5 mm²,
wire cross-section AWG/kcmil min. 24,
wire cross-section AWG/kcmil max. 12.
Spring force terminals:
nominal cross-section 2 x 1.5 mm²,
wire cross-section min. 0.2 mm²,
wire cross-section AWG min. 24,
wire cross-section AWG max. 16,
wire cross-section max. 1.5 mm².
Electrical data
Mains voltage:
BCU..Q: 120 V AC, -15/+10%, 50/60 Hz, ±5%,
BCU..W: 230 V AC, -15/+10%, 50/60 Hz, ± 5%.
Power consumption: 10 VA,
for grounded and ungrounded mains.
Flame control:
with UV sensor or flame rod.
For intermittent or continuous operation.
Flame signal current:
Ionization control: 1 – 25 μA,
UV control: 1 – 35 μA.
Ionization cable, UV cable:
max. 50 m (164 ft).
Contact rating:
Valve outputs V1, V2, V3 and V4 (terminals 60, 61,
62, 63 and 64): max. 1 A each, cos φ = 1.
Actuator outputs (terminals 65, 66 and 67):
max. 1 A each, cos φ = 1.
Air valve output (terminal 65): max. 1 A, cos φ = 1.
Ignition transformer (terminal 51): max. 2 A.
GB-29