Interface parameters
▷ Interface parameters I040 to I099 are set at the
factory and normally do not need to be adjusted.
CAUTION
Changing the default settings of the interface pa-
rameters will change the functions of the inputs
at terminals 1 to 41 and terminals 85 to 90, see
page 7 (Connection diagram).
Parameter name
Param-
eter No.
Parameter value
Flame control
0 = Ionization
1 = UVS
2 = UVC
3 = Ionization 1 and UVS 2
I004
4 = Ionization 1 and UVC 2
5 = UVS 1 and ionization 2
6 = UVC 1 and UVC 2
7 = UVC 1 and ionization 2
8 = UVC 1 and UVS 2
Air actuator
1 = IC 20
2 = IC 40
I020
3 = RBW
4 = Frequency converter
5 = Air valve
Function of terminal 64
0 = Off
I040
1 = Controller enable
2 = V5
3 = Bus output 1
Contact 80, 81/82 function
0 = Off
1 = Ready signal
2 = Air signal
3 = Purge signal
I050
4 = Cooling air valve
5 = Flue gas valve
6 = Fault signal
7 = Burner 1 operating signal
8 = Burner 2 operating signal
Contact 90, 91/92 function
I051
▷
See parameter I050 for parameter values
Function of contact 95/96
I052
▷
See parameter I050 for parameter values
Function of contact 95/97
I053
▷
See parameter I050 for parameter values
Contact 85/86, 87 function
I054
▷
See parameter I050 for parameter values
Parameter name
Param-
eter No.
Parameter value
Function of input 1
0 = Off
1 = Sensor 1
2 = Sensor 2
3 = Sensor 3
4 = Safety interlocks
5 = Air
6 = Cooling air
7 = Air actuator R1
8 = Air actuator R2
I061
9 = Start 1
10 = Start 2
11 = Reset
12 = Purge
13 = LDS
14 = HT
15 = Flame mode
16 = Flameless operation
17 = menox
19 = Auxiliary gas
Function of input 2
I062
▷
See parameter I061 for parameter values
Function of input 3
I063
▷
See parameter I061 for parameter values
Function of input 4
I064
▷
See parameter I061 for parameter values
Function of input 5
I065
▷
See parameter I061 for parameter values
Function of input 6
I066
▷
See parameter I061 for parameter values
Function of input 7
I067
▷
See parameter I061 for parameter values
Function of input 35
I068
▷
See parameter I061 for parameter values
Function of input 36
I069
▷
See parameter I061 for parameter values
Function of input 37
I070
▷
See parameter I061 for parameter values
Function of input 38
I071
▷
See parameter I061 for parameter values
Function of input 39
I072
▷
See parameter I061 for parameter values
Function of input 40
I073
▷
See parameter I061 for parameter values
Function of input 41
I074
▷
See parameter I061 for parameter values