Acsm1 Minimum Required Parameter Settings For Profinet - ABB ACS355 Series Quick Start Up Manual

Function blocks for siemens plc’s
Hide thumbs Also See for ACS355 Series:
Table of Contents

Advertisement

41

ACSM1 Minimum required parameter settings for PROFINET

The minimum required parameter settings based on factory default settings.
Parameter
Description
50.01
FBA ENABLE
51.01
FBA A ype
51.02
Protocol/Profile
51.04
IP Configuration
51.05 ...
IP address
51.08
51.09
Subnet CDR
51.27
FBA PAR
REFRESH
52.01
FBA DATA IN1
52.02
FBA DATA IN2
53.01
FBA DATA OUT1
53.02
FBA DATA OUT2
10.01
EXT1 START
FUNC
24.01
SPEED REF1
SEL
10.08
FAULT RESET
SEL
(25.02)
SPEED SCALING
Setting
Enable
Ethernet
PNIO ABB Pro (11)
Static (0)
192.xxx.xx.xx or any other
required IP address.
24
REFRESH
4
5
1
2
FBA
FBA REF1
P.02.12 bit 8
[Scale max]
Comment
Activates fieldbus module.
Filedbus type.
Communication profile ABB drives.
-
-
24 For subnet mask 255.255.255.0.
Updates fieldbus settings (groups 51
to 55).
Status word as Data Word 1 from the
drive.
Actual speed as Data Word 2 from
the drive.
Control word as Data Word 1 to the
drive.
Speed reference as Data Word 2 to
the drive.
Fieldbus interface as source for start
and stop.
Fieldbus interface as source for
speed reference.
Fieldbus interface as source for fault
reset.
Max speed/frequency scaling value
(used in function block/visualization
input SPEED_REF_MAX). Must be
less or equal to drive parameter max
speed/frequency.