Acs380 Minimum Required Parameter Settings Profibus Ds - ABB ACS355 Series Quick Start Up Manual

Function blocks for siemens plc’s
Hide thumbs Also See for ACS355 Series:
Table of Contents

Advertisement

17

ACS380 Minimum required parameter settings PROFIBUS DS

The minimum required parameter settings based on factory default settings.
Parameter
Description
50.01
FBA A Enable
51.02
NODE
ADDRESS
51.05
PROFILE
52.02
FBA data in2
53.02
FBA data out2
51.27
FBA par refresh
20.01
Ext 1
commands
22.11
Ext1 speed ref1
31.11
Fault reset
selection
(46.01)
Speed scaling
Setting
Comment
Enable
Activates fieldbus module
[PB NODE]
PROFIBUS DP node address of the drive
1
Communication profile ABB drives
Act1 16bit (5)
Actual speed as Data Word 2 from the drive
Ref1 16bit (2) Speed reference as Data Word 2 to the drive
Configure
Updates fieldbus settings (groups 50 to 57)
Fieldbus A
Fieldbus interface as source for start and stop
FB A ref1
Fieldbus interface as source for speed reference
P.06.01 bit 7
Fieldbus interface as source for fault reset
[Scale max]
Max speed/frequency scaling value (used in
function block/visualization input
SPEED_REF_MAX). Must be less or equal to
drive parameter max speed/frequency.

Hide quick links:

Advertisement

Table of Contents
loading