ACS850 Minimum required parameter settings for PROFINET

The minimum required parameter settings based on factory default settings.
Parameter
Description
50.01
Fba enable
51.01
FBA A type
51.02
Protocol/Profile
51.04
IP Configuration
51.05 ...
IP address
51.08
51.09
Subnet CDR
51.27
FBA PAR
REFRESH
10.01
Ext1 start func
10.10
Fault reset sel
(19.01)
Speed scaling
21.01
Speed ref1 sel
Setting
Enable
Ethernet
PNIO ABB Pro (11)
Static (0)
192.xxx.xx.xx or any other
required IP address.
24
REFRESH
FB
P.02.22 bit 8
[Scale max]
FBA ref1
Comment
Activates fieldbus module
Fieldbus type
Communication profile ABB drives
-
-
24 For subnet mask 255.255.255.0
Updates fieldbus settings (groups 51
to 55)
Fieldbus interface as source for start
and stop
Fieldbus interface as source for fault
reset
Max speed/frequency scaling value
(used in function block/visualization
input SPEED_REF_MAX). Must be
less or equal to drive parameter max
speed/frequency.
Fieldbus interface as source for
speed reference