Unit Schema - Carel kVent Manual

Controller for ventilation units
Table of Contents

Advertisement

3.2 Unit schema

DO9
A013
E
XHAUST
DO15
AO2
MB1
AI14
DI22
DO11
AI3
AI25
AO7
F
RESH
DI13
DI14
AI26
AI27
AI
Code
Analog input
1
Ga01
Supply temperature
2
Ga06
Return temperature
3
Ga11
External temperature
4
Ga16
Exhaust temperature
6
Ga26
Back water temperature
9
Ga41
Discharge temperature
10
Ga 46
Preheater back water temp.
11
Ga51
After preheater temp.
12
Ga56
CO2 sensor
13
Ga61
Supply air pressure
14
Ga66
Exhaust air pressure
15
Ga 71
Supply humidity
24
GaB6
VOC sensor
25
GaC1
Fresh air humidity
26
GaC6
Hepa filter 1
27
GaD1
Hepa filter 2
kVent – rel 3.1 – 22/06/2018
AI4
DO1
0
AO6
AO8
AI11
AI10
DI
Code
Digital input
1
Gb01
Fire alarm
2
Gb03
Fan overload
3
Gb05
Humidifier alarm
4
Gb07
Remote On
5
Gb09
Summer/Winter
6
Gb11
Cooling alarm
8
Gb15
Freeze alarm
9
Gb17
Heating alarm
10
Gb19
Eco
11
Gb21
Precomfort
12
Gb23
Comfort
13
Gb25
Supply filter alarm
14
Gb27
Supply filter alarm 2
15
Gb29
Return filter alarm
21
Gb41
Supply air flow switch
22
Gb43
Return air flow switch
23
Gb45
Recovery clogged
24
Gb47
Door Switch
26
Gb51
External generic alarm
DO35
AO11
DO2
DO4
DO1
AO5
AO3
DO5
AO4
DI6
DI8
DI9
AI6
DO
Code
Digital output
1
Gc01
Cool/Heat
2
Gc03
Cooling 1
3
Gc05
Cooling 2
4
Gc07
Heating 1
5
Gc09
Reverse 1
6
Gc11
Heating 2
7
Gc13
Reverse 2
8
Gc15
Reheat
9
Gc17
Exhaust air damper
10
Gc19
Recovery
11
Gc21
Preheater
12
Gc23
Humidifier
13
Gc25
Alarm
14
Gc27
Supply fan
15
Gc29
Exhaust fan
17-18
Gc33-35
Heat Op/Cl
19-20
Gc37-39
Cool Op/Cl
21-22
Gc41-43
Cool/Heat Op/Cl
23-24
Gc45-47
Heat rec Op/Cl
25-26
Gc49-51
Mix Op/Cl
27-28
Gc53-55
Preheat Op/Cl
29-30
Gc57-59
Reheat Op/Cl
35
Gc69
IEC humidifer
36
Gc71
Recovery step 1
37
Gc73
Recovery step 2
15
AI24
AI12
DI15
DO12
DO8
DI2
DO14
AO9
AI15
AO10
AO1
MB2
DI3
AI13
DI21
AO
Code
Analog output
MB
1
Gd01
Supply fan
1
2
Gd02
Exhaust fan
2
3
Gd03
Heating
4
4
Gd04
Reverse
5
Gd05
Cooling
6
Gd06
Heat recovery
7
Gd07
Preheater
8
Gd08
Mix
9
Gd09
Humidifier
10
Gd10
Reheater
11
Gd11
IEC
12
Gd12
Cool/Heat signal
13
Gd13
Fresh Damper
15
Gd15
Main cool req. Optional
17
Gd17
Main Heat req. Optional
19
Gd19
ReHeat req. Optional
20
Gd20
PreHeat req. Optional
AI2
MB4
DI10
DI11
DI12
DI4
AI1
DI1
DO13
DI5
ModBus®
Exhaust fan
Supply fan
th-Tune

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents