Routine Inspection/Maintenance - Vent-Axia VSC Series Installation And Wiring Instructions

Sabre short case sickle fans/sabre sickle plate fans, euroseries short cased axial fans/euroseries axial plate fans

Advertisement

ROUTINE INSPECTION/MAINTENANCE

THIS MUST BE UNDERTAKEN BY A COMPETENT PERSON.
ISOLATE UNIT FROM ELECTRICAL SUPPLY AND ENSURE THAT IT CANNOT BE ACCIDENTALLY
TURNED BACK ON.
1.
We recommend that after three months the fan should be inspected and cleaned to remove deposits on
the impeller or motor. Thereafter, it should be checked and cleaned periodically as experience dictates,
or at least twice a year.
2.
If a build up of dirt/deposits is evident then this should be carefully cleaned off. Please take care not to
damage the fan or affect the balance of the impeller motor assembly (balance weights may be fitted to
the impeller).
3.
The fan motors are fitted with 'sealed for life' bearings and should not require maintenance under normal
circumstances.
Wiring Diagrams:
Important Notes:- The electrical circuit must be protected with an all pole isolator having a minimum of 3mm
contact separation with suitable fuses or circuit breaker.
For ducted applications the Thermal Protector (TB) must be connected into a control circuit in order to ensure that the
fan cannot restart before the fault condition is cleared and the circuit manually reset.
(Refer to table below, for the relative wiring diagram – each fan has a wiring label within terminal box)
VA Part
Number
ESC25012
ESP25012
ESC25014
ESP25014
ESP25032
ESC31532
ESP31532
ESC31512
ESP31512
ESC31534
ESP31534
ESC31514
ESP31514
ESP35034
ESC35014
ESP35014
ESP35016
ESC40034
ESP40034
ESC40014
ESP40014
ESP40016
ESC45034
ESP45034
ESC45014
ESP45014
ESP45016
ESC50034
ESP50034
ESC50014
ESP50014
ESC56034
ESP56034
ESC56014
ESP56014
ESP56036
ESP56016
ESC63034
ESP63034
ESC63014
ESP63014
ESC63036
ESP63036
Wiring
Air Flow
Diagram
Direction
177X
177X
177X
177X
106XB
106XB
106XB
104XB
104XB
106XB
106XB
104XB
104XB
106XB
104XB
104XB
104XB
106XB
106XB
104XB
104XB
104XB
106XB
106XB
104XB
104XB
104XB
106XB
106XB
104XB
104XB
106XB
106XB
104XB
104XB
106XB
104XB
106XB
106XB
104XB
104XB
106XB
106XB
Reversible (note if yes 40%
reduction in airflow
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
Voltage
230
230
230
230
400
400
400
230
230
400
400
230
230
400
230
230
230
400
400
230
230
230
400
400
230
230
230
400
400
230
230
400
400
230
230
400
230
400
400
230
230
400
400

Advertisement

loading

This manual is also suitable for:

Esc seriesEsp seriesEsc25012Esp25012Esc25014Vsp series ... Show all