Measures Taken To Assure Emc; Cabling Power Unit - Baumuller BFN 3-1-0007-001 Instruction Handbook Manual

Filters for mains applications
Table of Contents

Advertisement

7.5.2

Measures taken to assure EMC

The following configuration notes must be considered to assure EMC.
Cabling
m All connected cables must be screened in order to suppress interfering radiation out-
Consider the information submitted in
Power
choke
Figure 13:
side the power converter. If the screening attenuation of the control cabinet is high
enough (see limit values of the interference emission complying with EMVG for your
system) and if the EMC-compatibility in the internal space is ensured (this can be as-
sumed if the configuration notes of this chapter are complied with), the control cables
can be mounted unscreened.

Cabling power unit

ZScreening–
on page 52.
Instruction handbook Mains filters BFN
Document No.: 5.09010.03
7
Installation
49
of 70