Wiring a room sensor to the SE6166
You can wire:
•
•
See the following sections for wiring instructions. For other details, see the RS Room
Sensors Technical Instructions or the LogiStat Sensors Technical Instructions.
Rnet wiring
NOTE Use the specified type of wire and cable for maximum signal integrity.
specifications
Description
Conductor
Maximum length
Insulation
SE6166 Controller • Rev. 4/13/2011
Connect the analog output wiring to the screw terminals on the SE6166 and to the
controlled device.
Set AO
Mode Select
jumper to...
Gnd
0-10 Vdc
Any AO
Gnd
0-10 Vdc
Any AO
Gnd
0-20 mA
Any AO
0-20 mA
Gnd
Any AO
Set the AO Mode Select jumper to the type of device you are wiring the output to.
Turn on the SE6166's power.
An RS Standard, RS Plus, RS Pro, or RS Pro-F to the SE6166's Rnet port
A LogiStat or LogiStat Plus to the SE6166's Lstat port
4 conductor, shielded or unshielded, CMP, plenum rated cable
22 AWG (7x0096) bare copper if Rnet has only RS sensors.
18 AWG (7x0152) bare copper if Rnet has a BACview.
500 feet (152 meters)
Low-smoke PVC (or equivalent)
Gnd
–
0-10 V
+
Hot
+
3-wire
–
Hot
0-10 V
+
+
Gnd
4-wire
–
0-20 mA
Hot
+
+
3-wire
–
Hot
0-20 mA
+
+
Gnd
4-wire
10
24 Vac/dc
© 2011 Automated Logic Corporation