Set Values For Monitoring The Winding Temperature; Test Run; Table 7-3 Set Value For Commissioning; Table 7-4 Set Values During Normal Operation - Siemens SIMOTICS FD 1MM1 Series Operating And Installation Instructions

Low-voltage motor
Table of Contents

Advertisement

Start-up

7.7 Set values for monitoring the winding temperature

7.7
Set values for monitoring the winding temperature
Prior to commissioning
Before running the machine for the first time, set the temperature value for shutdown on the
monitoring device.
Table 7-3
Set value
Alarm
Shutting down
Normal operation
1. Measure the normal operating temperature T
2. Set the values for shutdown and warning corresponding to the operating temperature T
Table 7-4
Set value
Alarm
Shutting down
7.8

Test run

After installation or inspection, carry out a test run:
1. Start up the machine without a load. To do this, close the circuit breaker and do not switch
2. If the machine is running smoothly and evenly, switch on the cooling equipment. Continue
100
Set value for commissioning
Set values during normal operation
off prematurely. Check whether it is running smoothly.
Switching the machine off again while it is starting up and still running at slow speed should
be kept to a bare minimum, for example for checking the direction of rotation or for checking
in general.
Allow the machine to run down before switching it on again.
to observe the machine for a while in no-load operation.
Temperature
at the installation location in ° C.
op
Temperature for insulation class 180(H), utilization 155(F)
T
+ 10 K ≤ 145° C
op
T
+ 15 K ≤ 155° C
op
145° C
155° C
SIMOTICS FD 1MM1
Operating Instructions 02/2019
.
op

Advertisement

Table of Contents
loading

Table of Contents