Electrical Connection - HB Products HBDF MK2 Instruction Manual

Defrost sensor “demand defrost”, for automatic defrosting of evaporators
Table of Contents

Advertisement

Parameter settings
Parameter
Enable Start/Stop
function
Enable mA only function
(PLC Control)
Defrost Start in %
Defrost stop temp.
Sensor delay in min.
(Used to ensure frost
condition before start
measuring)
Sensor lenght in mm.
between fins in mm.
Distance
CAUTION! In case of welding on the system, disconnect the power supply so that the electronics are not damaged during

Electrical connection

welding.
instruction manual - HBDF –mk2 – defrost sensor (013-UK) 19/03-2019 WWW.HBPRODUCTS.DK
WE INCREASE
UPTIME
AND
IN THE REFRIGERATION INDUSTRY
Description
Activate/deactivate the measuring and set the mA output to 4mA,
and set the digital relays to default.
Turn off the digital relays and also the timers. Only running with mA
output.
Defrost start in % where the digital start relay is activated and the
mA is lock when it get to the defrost start level. E.g. 50% stops the
mA output at 12mA.
Defrost stop temperature when the digital stop relay is activated
and the sensor delay starts running, mA only function is 19mA.
Sensor delay time is used for securing frost after defrost before the
sensor start measuring again. The start and stop relay is deactivated
after timeout.
The total length of the active part of the wire between the fins (only
the wire between the fins is active).
Distance between fins in mm.
EFFICIENCY
12 / 17