Installation; Hbdf-Snapon Clips - HB Products HBDF MK2 Instruction Manual

Defrost sensor “demand defrost”, for automatic defrosting of evaporators
Table of Contents

Advertisement

Installation

The following applies to system design:
1)
The sensor box is installed on the frame of the evaporator.
2)
Ground wire should be connected to the frame with a stainless screw.
3)
The wire must be placed between the fins in the air inlet side, or where ice build-up occurs.
The wire can be fixed with a special HBDF wire-clips or standard nylon (PA6) wire strips.
4)
The temperature sensor must be mounted between the fins at the bottom of the evaporator
section (to measure when all the ice has melted).
5)
Normally installed with a standard unshielded cable. If the EMC is higher than described in
EN 61326, a shielded cable must be used.
Note:
To have a proper ground connection, we recommend using stainless screw with a star washer/disc and cover/applying
silicone grease/compound around the connection to avoid corrosion.

HBDF-snapON Clips

instruction manual - HBDF –mk2 – defrost sensor (013-UK) 19/03-2019 WWW.HBPRODUCTS.DK
WE INCREASE
UPTIME
AND
EFFICIENCY
IN THE REFRIGERATION INDUSTRY
In this photo the wire is
secured with nylon Snap
On clips. Regular nylon
cable binders can also be
used.
Note that the arcehs of
the wire in the photo do
not extend beyond the
length of the fins.
See illustration next
page.
Piping in mm
Clips
8-10 mm
HBDF-snapONClips8
10-12 mm
HBDF-snapONClips10
12-14 mm
HBDF-snapONClips12
14-16 mm
HBDF-snapONClips14
16-18 mm
HBDF-snapONClips16
19-22 mm
HBDF-snapONClips19
22-25 mm
HBDF-snapONClips22